DOI QR코드

DOI QR Code

배전계통에 초전도한류기 적용시 OCR 및 Recloser 동작특성 분석

Analysis of Operation Characteristics of OCR and Recloser in Power Distribution System with SFCL

  • 문종필 (한국교통대 전기공학과)
  • 투고 : 2012.10.23
  • 심사 : 2012.11.20
  • 발행 : 2012.12.01

초록

In this paper, the method of protective coordination is studied to install Superconducting Fault Current Limiter (SFCL) to power distribution system. If SFCL is installed, the protective coordination is not operated well because of the decreased fault current. Thus, the resetting method of protective devices is presented to coordinate protection system in power distribution system with resistor-type SFCL. The presented methods are divided into three parts; OCR, OCR-Recloser, OCR-Recloser-Recloser. The presented methods are proved through case studies using PSCAD/EMTDC simulation.

키워드

참고문헌

  1. 안재민, 김진석, 문종필 외, "배전계통 초전도 전류 제한기 적용시 보호협조 분석", 대한전기학회 논문지, 제57권, 5호, 2008년 5월.
  2. T. Hara, T. Okuma, T. Yamamoto, D. Ito K. Tasaki, and K. Tsurunaga, "Development of a new 6.6kV/1500A class superconducting fault current limiter for electric power system," IEEE Trans. Power Delivery, Vol. 8, No. 1, pp. 182-192, Jan. 1993 https://doi.org/10.1109/61.180335
  3. H. Kameda, and H. Taniguchi, "Setting Mothod of Specific Parameter of a Superconducting Fault Current Limiter Considering the Operation of Power System Protection," IEEE Tranactions on Applied Superconductivity, Vol. 9, No. 2, June 1999
  4. B. W. Lee, J. Sim, K. B. Park, I. S. Oh, S. W. Yim, H. R. Kim, O. B. Hyun, "Fabrication and Tests of the 24kV class Hybrid Superconduction Fault Current Limiter", Journal of the Korea Institute of Applied Superconductivity and Cryogenics, Vol. 9, No. 4, pp. 32-36, 2007
  5. 김명후, 김진석, 유일경 외, "배전계통에 초전도 전류제한기 적용시 Recloser-Fuse 협조 방법에 관한 연구", 대한전기학회논문지 제 58권 10호, pp. 1385-1841, 2009 년 10월.
  6. 김진석, 임성훈, 문종필 외, "MTR 중성점 접지에 초전도 전류제한기 적용시 지락과전류계전기 동작 분석", 대한전기학회논문지 제 58권 11호, pp. 2089-2094, 2009 년 11월.
  7. 한전전력연구원, 22.9KV 배전 실증시험장 건설에 관한 연구, 기술보고서, 1995년.
  8. J. F. Moon, S. H. Lim, J. C. Kim, S. Y. Yun, "Assessment of the Impact of SFCL on Voltage Sags in Power Distribution System", IEEE Transactions on Applied Superconductivity, Vol. 21, No. 3, pp. 2161-2164, Jun 2011 https://doi.org/10.1109/TASC.2010.2093592