A Method to Monitor Vacuum Degree Using Capacitive Partial Discharge Coupler

  • Sun, Jong-Ho (HVDC Research Division, Korea Electrotechnology Research Institute (KERI)) ;
  • Youn, Young-Woo (HVDC Research Division, Korea Electrotechnology Research Institute (KERI)) ;
  • Hwang, Don-Ha (HVDC Research Division, Korea Electrotechnology Research Institute (KERI)) ;
  • Yi, Sang-Hwa (HVDC Research Division, Korea Electrotechnology Research Institute (KERI)) ;
  • Kang, Dong-Sik (HVDC Research Division, Korea Electrotechnology Research Institute (KERI))
  • Received : 2011.12.16
  • Accepted : 2012.04.28
  • Published : 2012.11.01

Abstract

Internal pressure of vacuum interrupter (VI) is one of the most important parameters in VI operation and may increase due to the outgassing from the materials inside VI or gas permeation through metal flange or ceramic vessel. The increase of the pressure above a certain level leads to the failures of switching or insulation. Therefore, an effective pressure check of VI is essential and an analysis of partial discharge (PD) characteristics is an effective monitoring method to identify the degree of the internal pressure of VI. This paper introduces a research work on monitoring the internal pressure of VI by analyzing PDs which were measured using a capacitive PD coupler. The authors have developed cost effective capacitive coupler based on the ceramic material that has an excellent insulation properties and the main component of the capacitive coupler is made by SrTiO3. Detectable internal pressure range and distinguishability of the internal pressure of VI were investigated. From the PD tests results, the internal pressure range, from $10^{-2}$ torr to 500 torr, can be monitored by PD measurements using the capacitive coupler and PD inception voltage (PDIV) follows the Paschen's law. In addition, rise time of PD pulse at 13.2kV decreases with the increase of the internal pressure of VI.

Keywords

References

  1. Y. Matsui et. al., "Development and technology of high voltage ACBs; brief history and state art: ", XXIInd Int. Symp. On Discharge and Electrical Insulation in Vacuum-Mastue, 2006.
  2. H. Saitou et. al., "Determination of Gas Pressure in Vacuum Interrupter Based on Partial Discharge", IEEE Trans. On DEI Vol. 14, No. 3, June, 2007.
  3. F. R. Frontzek et. al., "Methods for internal pressure diagnostic of vacuum circuit breakers", 18th international symposium on discharge and electrical insulation in vacuum, 1988.
  4. L. Falkingham, "Vacuum life assessment of a sample of long service vacuum interrupters", 20th CIRED, Prague, June, 2009.
  5. IEC 62271-1, "High-voltage switchgear and control gear - Part 1: Common specifications".
  6. M. Kamarol et. al., "Diagnosis of vacuum degree in vacuum interrupter based on partial discharge", XXIInd Int. Symp. On Discharge and Electrical Insulation in Vacuum-Matsue, 2006.
  7. D. F. Grosjean, "Development of procedures for partial discharge measurements at low pressures in air, argon, helium", IEEE Trans. On DEI Vol. 15, No. 6 , 2008.

Cited by

  1. A pilot study on the vacuum degree online detection of vacuum interrupter using laser-induced breakdown spectroscopy vol.49, pp.44, 2016, https://doi.org/10.1088/0022-3727/49/44/44LT01