Algorithm for Preventing Malfunction and Reclosing in Grid-Connected PV Systems

연계형 태양광발전설비의 새로운 오동작 방지 및 재병입 알고리즘 제안

  • 황민수 (서울과학기술대학교 산업대학원 전기공학과) ;
  • 전태현 (서울과학기술대학교 전기정보시스템공학과)
  • Received : 2012.05.22
  • Accepted : 2012.06.20
  • Published : 2012.07.31

Abstract

In general, the unidirectional power flow is normal in distribution feeders before activation of distributed power source such as PV. However, the interactive power flow is likely to occur in case of the power system under distributed generation. This interactive power flow can cause an unexpected effect on convectional protection coordination systems designed based only on the unidirectional power flow system. When the power line system encounters a problem, the interactive power flow can be a contributed current source and this makes the fault current bigger or smaller compared to the unidirectional case. The effect of interactive power flow is varied depending on the location of the point to ground fault, relative location of the PV, and connection method. Therefore it is important to analyse characteristics of fault current and interactive flow for various transformer connection and location of the PV. This paper proposes a method of improved protection coordination which can be adopted in the protective device for customers in distribution feeders interconnected with the PV. The proposed method is simulated and analysed using PSCAD/EMTDC under various conditions.

Keywords

References

  1. New & Renewable Energy Statistics 2010, Korea Energy Management Corporation, 2011. 11.
  2. Dong-yeol Shin, Dong-myung Kim, Han-Ju Cha, "An Overcurrent Analysis in Neutral Line and Algorithm to Prevent Malfunction of Relay in Distributed Generations" KIEE, vol.58, no.8, pp. 1916-1922, 2008. 8.
  3. Dong-yeol Shin, Yong-woo Park, Han-Ju Cha, "A Case Study on Malfunction of OCGR and Inaccuracy of Watt-hour Meter in Distributed Generation System", KIEE, vol.57, no.8, pp. 1349-1355 2008. 8.
  4. Chan-Hyeok KIM, Yong-Pil Wang, Woo-Ho Kim, Joonho Ahn, Dae-Seok Rho "A Study on the Characteristics Analysis of Fault according to the Winding of Transformer to connect the distributed generation in Distribution System" KIIEE Conference Proceedings, 2010. 5.
  5. Chan-Hyeok KIM, Hyeon-Seok Park, Dea-Seok Rho, Chang-Hoon Shin, Gi-gab Yoon "A Study on the Optimal Method for Mal-function of Re-closer at the Distribution Feeders Interconnected with PV Systems" KIEE, vol.58, no.10, pp. 1512-1518, 2009. 10.
  6. 'Distributed Generation to Connect Distributed System Technical Regulation' KEPCO Distribution Construction Department, 2010. 3.
  7. 'Distributed Generation to Connect Distributed System Guideline' KEPCO Distribution Construction Department, 2010. 3.
  8. Dong-yeol Shin, (2009) "An Analysis and Countermeasure for the Reverse-Power-Flow Phenomena of Distribution System Interconnected with Distributed Generations" Thesis, Chungnam National University.
  9. Chan-Hyeok KIM, (2010), "A Study on the Bidirectional Protection Coordination Method in Distribution Systems with Dispersed Generation", Thesis, Korea University of Technology and Education.
  10. Development of Fault Analysis Evaluation System for Dispersed Power Sources in Distribution Systems, Research Report, ERIK, 2009. 8.