In this study, we have investigated the effect of the solar power generation facilities on the power quality of interconnected solar power generation system. When the solar power generation facility was connected to the distribution system, whether the solar power generation is under operation or not, Peak factor of current was increased to 0.033[%], Frequency is deviated from $60{\pm}0.2$[Hz] and also Short term flicker indication($P_{st}$) increased to 0.213[p.u.] compare with the disconnected situation. Harmonic current [%] in orders was 11.42[%] maximum under 11th orders and was 7.861[%] between 11th and 17th orders. These values were about 3 or 4 times compared with "the power system interconnection technique standards" at the same situation above. Therefore, we could confirmed that the solar power generation facility, when it was connected to the existing distribution system, made bad influence on the power qualities such as the peak factor of current, frequency regulation, short term flicker indication($P_{st}$) and harmonic current [%] in orders etc.

키워드

참고문헌

  1. The Technical Guideline for the Grid Connection of the Substitution Energy Generation System. Ministry of Commerce, Industry and Energy, Final Report, 2004. 6.
  2. The Newest Distribution System Engineering, KIEE, Bookshill, 2006.
  3. "IElectromagnetic compatibility (EMC) - Part 4-15: Testing and measurement techniques - Flickermeter - Functional and design specifications", IEC 61000-4-15 Ed. 2.0 b:2010.
  4. Business 0100 The Basic Rules and Rates for Electric Service, KEPCO, 2007. 7.
  5. Business 0900 The Regulation for the Use of the Distribution Electric Power Facility. KEPCO. 2006. 9.
  6. The Electric Power System Reliability and Electricity Quality Maintenance Criteria. Notification of Ministry of Commerce, Industry and Energy volume 2005-11, 2005. 1.
  7. "IEEE Recommended Practice for Emergency and Standby Power Systems for Industrial and Commercial Applications", IEEE Std 446-1995.
  8. "IEEE Recommended Practices and Requirements for Harmonic Control in Electrical Power System", IEEE Std 519-1992.
  9. Business 0110 The Basic Rules and Rates for Electric Service, The Detailed Enforcement, 2007. 8.
  10. The Technological Standard for the Connection in the Distribution Power System of the Distributed Energy Resource, KEPCO, 2007, 4.