DOI QR코드

DOI QR Code

Coating formation of water supply pipes by inhibitor and water quality improvement effect

부식억제제에 의한 상수도관의 피막 형성 및 수질개선 효과

  • Published : 2012.02.15

Abstract

To investigate the application of corrosion inhibitor on water supply pipes, turbidity, magnitude of corrosion, composition of scale and concentration of metals from an old steel pipe were analysed under inhibitor addition. The concentration of turbidity, iron and copper from the pipes under inhibitor application was 12 ~ 14% of the case which no inhibitor was applied, which suggests the application of inhibitor was very effective for internal corrosion control. In addition, SEM, EDX, XRD and XRF test results showed that application of inhibitor was effective for the decrease of iron concentration and increase of oxygen, phosphorus and calcium concentration, which suggested the existence of protective layer. Therefore, the occurrence of red water will be significantly decreased when inhibitor was applied to the old steel pipes.

Keywords

References

  1. 김진근, 김영관 (2011) 국내 수돗물의 부식성 특성 및 개선 방안, 상하수도학회지, 25(5). pp. 731-739
  2. 유순주, 박수정, 안경희, 김현구, 김창수, 정일록, 박영복 (2008) 수돗물 수질에 따른 옥내급수관 부식에 미치는 영향 분석, 상하수도학회지, 24(6). pp. 701-708
  3. 이병두 (2004) 상수도 배급수관 내부부식방지를 위한 부식억제제의 적용, 충북대학교 환경공학과 박사학위논문
  4. 임재철 (2010) 노후 상수도관에 대한 인산염 부식억제제의 현장 적용성 연구, 서울시립대학교 환경공학과 석사학위논문
  5. 정원석, 김진근, 박덕준, 김선욱, 정상기 (2011) 소석회와 이산화탄소를 이용한 수돗물 부식성 제어에 관한 연구, 상하수도학회지, 25(2) pp. 193-199.
  6. 한국상하수도협회 (2008) 수처리제의 적정 사용관리 방안 연구
  7. 환경부 (2011) 상수도통계
  8. 환경부 (2007) 환경부고시 제2007-92호.
  9. AWWA (1986) Corrosion control for operators.
  10. AWWARF and VGW-TZW (1996) Internal corrosion of water distribution systems, AWWARF.
  11. Edwards, M., Hidmi, L., Gladwell, D. (2002) Phosphate inhibition of soluble copper corrosion by-product release, Corrosion Science, 44, 1057-1071 . https://doi.org/10.1016/S0010-938X(01)00112-3
  12. Sarin, P., Clement, J.A., Snoeyink, V.L, Kriven, W.M. (2003) Iron release from corroded, unlined cast-iron pipe, J. of American Water Works Association, 95(11), 85-96.
  13. Schock, M.R., Lytle, D.A. (2011) Internal corrosion and deposition control in Water Quality and Control 6th Ed. Mc-Graw Hill, New York.
  14. USEPA homepage (2011) http://water.epa.gov/drink/contaminants/index.cfm

Cited by

  1. Study on characteristic for Larson's ratio of water treatment plants vol.30, pp.5, 2016, https://doi.org/10.11001/jksww.2016.30.5.579
  2. Developing a Model for Controlling Internal Corrosion in Water Supply System vol.09, pp.02, 2017, https://doi.org/10.4236/jwarp.2017.92013