DOI QR코드

DOI QR Code

Dielectric Breakdown Voltage According to Flow Velocity and Temperature of Vegetable Oils

식물성절연유의 유동속도와 온도에 따른 절연파괴전압

  • Received : 2011.09.21
  • Accepted : 2012.04.25
  • Published : 2012.06.01

Abstract

The streaming electrification process of vegetable insulating oils occurring when the oils contacted with solid material in a high power transformer circulation system seems to cause electrical discharge incidents and may cause failures. We therefore measured the dielectric breakdown voltage tendency of vegetable insulating oils flowing on the surface of the charging device with various velocity and temperature. First, the relation between the velocity and breakdown voltage tendency of vegetable oils, can be explained by volume effect and v-t effect. Second, experimental results show that applied voltage have little effect on dielectric breakdown voltage, when vegetable insulating oils used for large power transformer.

Keywords

References

  1. McShane, C.P., Corkran, J., Rapp, K., Luksich, J., " Natural Ester Dielectric Fluid Development", 2005/6 IEEE PES Transmission and Distribution Conference and Exhibition, pp.18-22, 2006.
  2. E.Moreau, T.paillat, G.Touchard, "Flow electrification in High Power Transformer : BTA Effect on Pressboard Degraded by Electrical Discharges", IEEE Transactions on Dielectric and Electrical Insulation, Vol.10, No.1, pp.15-21, 2003. https://doi.org/10.1109/TDEI.2003.1176551
  3. 김정태, "고전압 이론과 응용(Theory ans Applications of High Voltage Engineering)", 교우사
  4. Tomoyuki Hikosaka, Akina Yamazaki, Yasunori Hatta et al., "Development of a New Environment-conscious Transformer Impregnated with Palm Fatty Acid Ester(PFAE)", IEEJ Transactions on Power and Energy, Vol.129, No.11, pp. 1397-1402, 2009. https://doi.org/10.1541/ieejpes.129.1397
  5. 이병성, "식물성절연유를 사용한 배전용 변압기의 절연 및 냉각특성 해석(Analysis on the insulation and cooling characteristic of distribution transformer using the natural ester)", 충남대학교 대학원, 2006.
  6. Chang-Su Huh, Jung-Il Jeong, "Study on the Streaming Electrification of Insulating oil under Electricfield", The Journal of the Korean Institute of Electrical and Electronic Material Engineers, Vol. 10, No.4, pp.314-241, 1997.
  7. KS C IEC 60156, "Insulation liquids-Determination of the breakdown voltage at power frequency - test method", 2003.
  8. 김종길, 이명의, "고전압 방전 플라즈마 : 이론 및 응용 (High Voltage Electric Discharge Plasma & Application), 인터비전.
  9. K. Koto, X. Han a, H. Okubo, "Insulation optimization by Electrode Contour Modification Based on Breakdown Area/Volume Effects", IEEE Transaction on Dielectric and Electrical Insulation, Vol.8, No.2, 2001.