Abstract
Korea Ministry of Knowledge Economy has estimated that wind power (WP) will be occupied 37% in 2020 and 42% in 2030 of the new energy sources, and also green energies such as photovoltaic (PV) and WP are expected to be interconnected with the distribution system because of Renewable Portfolio Standard (RPS) starting from 2012. However, when a large scale wind power plant (over 3[MW]) is connected to the traditional distribution system, protective devices (mainly OCR and OCGR of re-closer) will be occurred mal-function problems due to changed fault currents it be caused by Wye-grounded/Delta winding of interconnection transformer and %impedance of WP's turbine. Therefore, when Double-Fed Induction Generator (DFIG) of typical WP's Generator is connected into distribution system, this paper deals with analysis three-phase short, line to line short and a single line ground faults current by using the symmetrical components of fault analysis and PSCAD/EMTDC modeling.
2008년도 지식경제부의 전망에 의하면 신재생에너지전원 중 풍력발전의 보급전망은 2020년 37%, 2030년 42%에 달하고, 2012년부터 시행 예정인 신재생에너지 의무할당제(Renewable Portfolio Standard-RPS)의 도입으로 태양광 및 풍력 등의 신재생에너지가 향후 지속적으로 배전계통에 연계 운용될 것으로 예상된다. 현재 풍력은 배전계통에 전용선로로 연계되어 계통에 미치는 영향은 미미하지만, 3[MW] 이상의 대규모 풍력발전이 일반 배전선로로 확대 운용되면, 풍력발전 연계용 변압기 및 풍력발전기의 %임피던스에 의한 사고전류 변동으로 보호계전기(OCR, OCGR)의 오 부동작을 야기할 수 있다. 따라서 본 논문에서는 대표적인 풍력발전기인 이중여자유도발전기(Double-Fed Induction Generator-DFIG)가 고압 배전선로에 연계되어 운전되는 경우, 3상단락, 2선단락 및 1선지락의 사고특성을 분석하기 위하여, 전력계통 상용소프트웨어인 PSCAD/EMTDC를 이용하여 풍력발전기의 모델링과 시뮬레이션을 수행하고, 대칭좌표법을 통한 이론적인 수치해석의 결과치를 비교/분석하여, 제안한 수법의 유용성을 확인하였다.