Abstract

Compared to Packaged Terminal Air Conditioning Systems, Radiant Cooling Systems have the advantage of energy saving and thermal comfort. Thermally Activated Building System (TABS) is one of the radiant heating and cooling systems. The main difference between TABS and other radiant systems lies in the usage of the time-lag effect of storing heat energy in the concrete. Current energy usage in summer time is concentrated within a specific time by using Packaged Terminal Air-Conditioner (PTAC). Due to the time-lag effect of TABS, energy usage can be distributed to other time zones. To maximize this effect, it is important to determine the appropriate operating mode, which for TABS is dependent upon the cooling load generated by the occupancy schedule. In this study, occupancy schedules are determined for various residential types. The operating modes of TABS for these residential types are estimated by using a dynamic computational simulation method. The results indicate that the operating modes of TABS can be determined by residential type and occupancy schedule. The load handled ratio by TABS is set up differently according to the cooling load profile obtained from residential type and occupancy schedule. By using TABS, energy consumption could be reduced by 20% compared to PTAC.

Keywords

References

  1. ASHRAE (2008). ASHRAE Handbook HVAC Systems and Equipment, 2008.
  2. Babiak, J., Olesen, B. W., & Petra , D. (2007). Low temperature heating and high temperature cooling. Rehva.
  3. CEN (2009). EN 1264 Heating system in buildings, CEN.
  4. Chung, W. et al. (2011). Feasibility of a thermally activated building system in residential buildings. ISES Solar World Congress 2011, Kassel.
  5. ISO 7730: Ergonomics of the thermal environment - Analytical determination and interpretation of thermal comfort using calculation of the PMV and PPD indices and local thermal comfort criteria. (2005).
  6. National Statistical Office (2010). Ordinary households and household members by generations in household.
  7. National Statistical Office (2009). Participation average time spent on activities by age group.
  8. Park, S. et al. (2011). Operation mode of a thermally activated building system according to the starting time and the operating hours in residential building. ISES Solar World Congress 2011, Kassel.
  9. Park, S., Kim, I., Koo, S., Yeo, M., & Kim, K. (2010). The effect on the heat output by combination of design factors of thermally activated building system (TABS). Journal of the Korean Institute of Architectural Sustainable Environment and Building System, 4(3), 180-186.
  10. Yoo, M. et al. (2011). Evaluation on energy performance of thermally activated building system (TABS) in residential building. Proceeding of Autumn Annual Conference of the Architectural Institute of Korea, Planning & Design, 31(2), 399-400.