The plate fin and tube type of heat exchanger is widely used in air conditioner, and the heat exchanger is assembled by the mechanical expansion of copper tubes and fastening the aluminum fin. The objective of the present study is to investigate how the mechanical expansion of copper tube affects on the heat transfer performance of a plate fin and tube type heat exchanger. This study has been performed by experimental and numerical methods. The numerical and experimental results show that the tube expansion ratio has a influence on the heat transfer performance. Within the tested expansion ratio, the contact pressure shows the peak value and it decreases as the expansion ratio increases. Air-side heat transfer coefficient increases until the expansion ratio reaches 1.23, and then decreases with the similar pattern to the contact pressure. Also, contact heat transfer coefficient shows the maximum when the contact pressure is highest as well as the air-side heat transfer coefficient.

키워드

참고문헌

  1. The recent movements of heat exchanger development, 2008, Magazine of the SAREK, Vol. 37, No. 2, pp. 4-41.
  2. Jeong, J., Kim, C. N., and Youn, B., 2006, A study on the thermal contact resistance in fintube heat exchanger with 7 mm tube, International Journal of Heat and Mass Transfer, Vol. 49, No. 7, pp. 1547-1555. https://doi.org/10.1016/j.ijheatmasstransfer.2005.10.042
  3. Sawada, N., 2006, Measurement of thermal contact conductance between fin collar and tube, Proceedings, JSRAE Annual Conference, Fukuoka, pp. 161-164.
  4. Fujino, H., Kamada, T., Yoshioka, S., and Kasai, K., 2007, Effect of thermal contact resistance on fin-tube heat exchanger performance, Proceedings, JSRAE Annual Conference, Tokyo, pp. 285-289.
  5. Park, Y., Jeong, Y., Lee, J., and Park, N., 2009, Heat transfer characteristic of finned-tube heat exchangers with different clearance between fin collar and tube surface, Proceedings of the SAREK summer conference, pp. 1073-1078.
  6. Suzuki, H., Hashizume, S., Yabuki, Y., Ichihara, Y., Nakajima, S., and Kenmochi, K., 1968, Report of the Institute of Industrial Science, The University of Tokyo, Vol. 18, No. 3.
  7. JSME, 1986, JSME Data book-Heat transfer, 4th Ed., JSME Tokyo, pp. 30-31.
  8. Ishibashi, A., Kaga, K., Mukouyama, T., and Tadokoro, T., 2008, Design of compact heat exchanger for air conditioner indoor unit, Proceedings JSRAE Annual Conference, Osaka, pp. 77-80.
  9. ASME, 1985, Supplement on instruments and apparatus-Measurement uncertainty, Part 1, ASME New York.