DOI QR코드

DOI QR Code

A Study on the Effect of Integrated Leakage Rate Testing of Containment Vessel due to the Type A Testing Time

격납건물 ILRT 본시험시간이 시험에 미치는 영향에 관한 연구

  • 김창수 (한국수력원자력 중앙연구원) ;
  • 문용식 (한국수력원자력 중앙연구원)
  • Received : 2012.08.08
  • Accepted : 2012.11.11
  • Published : 2012.12.01

Abstract

The containment Integrated Leakage Rate Testing(ILRT) of nuclear power plants in Korea is performed in accordance with NSSC(Nuclear Safety and Security Commission) code 2012-16 and ANSI/ANS 56.8-1994. Nuclear power plants in Korea and the United States are to apply same test criteria, ANSI/ANS 56.8-1994, except type A testing time. NPPs in Korea apply 24 hours according to NSSC code 2012-16, but NPPs in United States apply 8 hours according to 10CFR50 App. J for type A test. So, there are many difficulties in order to perform ILRT in Korea. In this study, I review the impact on the ILRT results and the effect of ILRT due to type A testing time. The future, we will continue study to enhance the test reliability and improve these problems.

Keywords