Abstract
This study was conducted to analyze the thermal behavior of a PHC energy pi1e system in saturated soil conditions, various seasonal and flow-speed conditions during 100 hours of operation through numerical analysis. The examination was a1so conducted with a single pile as well as with group pils. For the operation of 100 hours, the average heat exchange rate appeared 55 W/m, 47 W/m during winter and summer respectively. An increase in flow-speed was associated with a rise in the heat exchange rate. And thermal behavior analysis results during winter season show that thermal efficiency has increased when there are more free thermal planes. For the operation in group pile as 3D and 5D pile spacing (D: pile diameter), average heat exchange rate increased as pile spacing grows. Compared with the heat exchange rate of single pile, thermal exchange efficiency of group pile decreased by 89% (for 3D spacing) and 93% (for 5D spacing).
본 논문에서는 지열을 이용한 PHC 말뚝형 에너지 파일의 계절별 유속변화에 따른 열교환율과 단독말뚝의 열교환율을 100시간 운용 시 포화지반 조건에 한정하여 수치해석을 수행하였다. 해석결과 동절기 및 하절기일 때 100시간 운용 시 평균 열교환율은 약 55 W/m, 47 W/m로 나타났으며, 순환수 유속이 증가할수록 전체적인 열교환율이 상승하였다. 동절기에 말뚝간격 3D 및 5D(D:말뚝직경) 배치 시 0.6m/s의 순환수 유속에 따른 열적거동을 분석결과 지반과의 열적 자유면이 많은 외곽부일수록 열효율이 증가하였다. 또한, 3D 및 5D 간격의 평균 열교환율은 약 48.5 W/m, 51 W/m로 말뚝간격이 증가할수록 열교환율이 향상되는 것으로 나타났으며, 단독말뚝의 열교환율 대비 상대적으로 3D 및 5D 간격의 군말뚝은 각각 89% 및 93%보 떨어지는 것을 알 수 있었다.