DOI QR코드

DOI QR Code

A Study on the Safety Diagnosis for Electric Power Systems Using Thermal Imaging Analysis

열화상 분석을 이용한 전력시스템의 안전진단에 관한 연구

  • Yu, Byeong-Yeol (Graduate School of Energy and Environment, Seoul National University of Science and Technology) ;
  • Kim, Chan-O (Department of Safety Engineering, Seoul National University of Science and Technology)
  • 유병열 (서울과학기술대학교 에너지환경대학원) ;
  • 김찬오 (서울과학기술대학교 안전공학과)
  • Received : 2011.02.12
  • Accepted : 2011.04.11
  • Published : 2011.04.30

Abstract

In this paper, the safety diagnosis using thermal image analysis is described for power equipments. The conventional three-phase comparison method has only provided the results of thermal comparison for the equipments. The proposed method defines the conditions of poor connection by visual checks, and supports the criteria with each thermal rise step. As a result, the thermal difference from $5^{\circ}C$ to $10^{\circ}C$ meant the warning state. In addition, the thermal difference more than $10^{\circ}C$ meant that the connection status was unbalanced. In this case, the countermeasure might be the internal load distribution. If the thermal difference more than $20^{\circ}C$ is observed, it means a hot spot at the poor connection. If the hot spot is observed all over the surface, its cause was the unbalanced load, which made the conductive parts discolored and raised the possibility of oxidization or $Cu_2O$ generation. This diagnostic technology employing thermal image analysis method can be directly applied in the field and ensures the safety of equipments.

Keywords

References

  1. 임용배, "열과 온도계측 및 열화상에 대한 소고", KIIEE Vol.18, No.5, pp. 24-31, 2004.
  2. 이동영, "파괴 및 비파괴진단 비교분석을 통한 케이블 열화특성평가", KIIEE Vol. 23, No. 6, pp. 104-108, 2009. https://doi.org/10.5207/JIEIE.2009.23.6.104
  3. 김종겸, 박영진, "전압 및 주파수 변동에 따른 콘덴서 열 분포 해석", 2009 KIIEE 추계학술, pp. 33-36, 2009.
  4. 유병열, "적외선열화상진단장비" 월간전기 7월호, pp. 76-78, 2008.
  5. 김동우, 문현욱, 김향곤, 길형준, 김동욱, 이기연, "분전함내 차단기 접속단자의 체결토크 변화에 따른 발열특성 및 화재위험성 분석", 2009 KIEE 추계학술, pp. 128-129, 2009.
  6. 임용배, 정종욱, 정진수, 고원식, "열화상을 이용한 몰드변압기 권선표면 진단", 2005 KIEE 추계학술, pp.107-108, 2005.
  7. 지식경제부 "전기재해통계분석", 제19호, pp. 19, 2010.
  8. 이충훈, 박성철, "적외선 온도카메라를 이용한 분할형 전기히터 가열 및 유동조건에 따른 전기히터와 매연필터 표면에서의 온도분포에 관한 연구", 한국안전학회지, 제23권, 제5호, P9, 2008.