DOI QR코드

DOI QR Code

A Study on the Optimal Design of Large-scale Photovoltaic Array

대용량 PV 어레이의 최적설계에 관한 연구

  • 황인호 (충북도립대학 전기에너지시스템과) ;
  • 김의환 (한국전력공사 전력연구원) ;
  • 안교상 (한국전력공사 전력연구원)
  • Received : 2010.10.08
  • Accepted : 2010.12.06
  • Published : 2011.02.28

Abstract

Recently, a number of large-scale photovoltaic(PV) power generation system has been installed all over the world. Thus, in order to improve the system efficiency, the optimal design of the large-scale PV systems has become an important issue. DC cable loss of PV array is one of the design factors related to the system efficiency. This paper introduces the array design method of a 500kW Photovoltaic power plant. Three types of the PV array are suggested. Also, string cables, sub-array cables and array cables are designed within 1% of voltage drop in the line, and the DC cable losses are analyzed. The results of this paper show that the DC cable loss of large-scale PV array can be reduced by adopting a proper sub-array design method.

Keywords

References

  1. 조덕기 외, "국내 최대 경사면 일사량 분석 " VOL.29, NO.1, 한국태양에너지학회 춘계학술대회 논문집, 2009.4.10.
  2. 이원교 편저, 전기설비의 설계 및 시공, 동일출판사,1998
  3. IEC 62257-7-1, Recommendations for small renewable energy and hybrid systems for rural electrification, Part7-1:Generators -Photovoltaic arrays
  4. 내선규정, 대한전기협회, 2006
  5. KSC IEC 60364-7-712 건축전기설비-제7부 712절 태양전지 전원시스템.
  6. 신재생에너지설비의 지원․설치․관리에 관한 기준,산업자원부 고시 제2008-3호.
  7. 이현화, 저탄소 녹색성장을 위한 태양광발전, (주)도서출판 기다리, 2009