DOI QR코드

DOI QR Code

An Analysis of the Ground Surface Potential Rise and Hazardous Voltages Caused by Impulse Currents

임펄스전류에 의한 대지표면전위상승 및 위험전압의 분석

  • 이복희 (인하대학교 IT공대 전기공학부) ;
  • 이규선 (인하대학교 IT공대 대학원 전기공학부) ;
  • 최종혁 (인하대학교 IT공대 대학원 전기공학부) ;
  • 성창훈 (인하대학교 대학원 전기공학과)
  • Received : 2011.02.10
  • Accepted : 2011.03.10
  • Published : 2011.04.30

Abstract

Lightning and switching surges propagating through the grounding conductors lead to transient overvoltages, and electronic circuits in information technology systems are very susceptible to damage or malfunction from the electrical surges. Surge damages or malfunctions of electrical and electronic equipment may be caused by potential rises. To solve these problems, it is very important to evaluate the ground surface potential rises and hazardous voltages such as touch and step voltages at or near the grounding systems energized by electrical surges. In this paper, the performance of grounding systems against the surge current containing high frequency components on the basis of the actual-sized tests is presented. The ground surface potential rises and hazardous voltages depending on impulse currents for vertical or horizontal grounding electrodes are measured and analyzed. Also the touch and step voltages caused by the impulse currents are investigated. As a result, the ground surface potential rises, the touch and step voltages near the grounding electrodes are raised and the conventional grounding impedances are increased as the front time of the injected impulse currents is getting faster.

Keywords

References

  1. 이복희, 이승칠, “접지의 핵심 기초 기술”, 도서출판 의제, pp.1-18, 1999.
  2. IEEE Std. 80-2000, “IEEE Guide for Safety in AC Substation Grounding”, pp.3-25, 2000.
  3. R. Kosztaluk, K. Mukhedkar, Y. Gervais, “Field measurements of touch and step voltages”, IEEE Trans., Vol.PAS-103, No.11, pp.3286-3294, 1984. https://doi.org/10.1109/TPAS.1984.318571
  4. G. Parise, M. Lucheroni, “Measurements of touch and step voltages adopting current auxiliary electrodes at reduced distance”, IEEE Trans. Industry Application, Vol. 44, No. 6, pp. 1896-1901, 2008. https://doi.org/10.1109/TIA.2008.2006349
  5. B. R. Gupta, B. Thapar, “Impulse Impedance of Grounding Grids”, IEEE Trans., Vol.PAS-99, No.6, pp.2357-2362, 1980. https://doi.org/10.1109/TPAS.1980.319800
  6. Silverio Visacro, “A Comprehensive Approach to the Grounding Response to Lightning Currents”, IEEE Trans. on P.D., Vol. 22 No. 1, 2007. https://doi.org/10.1109/TPWRD.2006.876707
  7. Leonid Grcev, “Impulse Efficiency of Ground Electrode”, IEEE Trans. Power Del.. Vol.24, No.1, pp.441-451, 2009. https://doi.org/10.1109/TPWRD.2008.923396
  8. IEC 62305-1, “Protection against lightning - Part 1: General principles”, 2006.
  9. IEEE Std. 81.2-1991, “IEEE Guide for Measurement of Impedance and Safety Characteristics of Large, Extended or Interconnected Grounding Systems”, pp.12-17, 1991.
  10. 최영철, 최종혁, 이복희, 전덕규 “수직 또는 수평으로 매설된 접지전극의 접지임피던스 측정시 보조전극 위치에 따른 전자유도의 영향”, 조명.전기설비학회 논문지, Vol. 23, No.8, pp.86-92, 2009. https://doi.org/10.5207/JIEIE.2009.23.8.086
  11. 최종혁, 최영철, 이복희, “수직 접지전극의 접지임피던스 측정에서 도전유도에 의한 오차 평가”, 전기학회 논문지, Vol.58, No. 9, pp.1778-1783, 2009.
  12. J. H. Choi, J. H. Kim, B. H. Lee, Y. K. Chung, “An analysis of conventional grounding impedance based on the impulsive current distribution of a counterpoise”, Proc. Conf. on ICLP, pp.1179-1-6, 2010.
  13. J. He, R. Zeng, Y. Li and B. Zhang, “Lightning Impulse Property of Vertical Grounding Rod”, Proc. Conf. on 28th ICLP, Vol.2, pp.686-691, 2006.