DOI QR코드

DOI QR Code

Analysis on the Chemical and Electrical Characteristic of Vegetable oil by Accelerated Aging

가속열화에 따른 식물성절연유의 화학적.전기적 특성 분석

  • Received : 2011.02.16
  • Accepted : 2011.04.14
  • Published : 2011.05.01

Abstract

Electrical insulation is one of the most important part in a high voltage apparatus. Recently, researchers are interested in the environmental friendly vegetable oil from environmental viewpoint. Accelerated aging transformer insulating material in vegetable oil was compared to that of mineral oil. Accelerated aging oil samples produced in the oven at $140^{\circ}C$ for 500, 1000, 1500, 2000hours. And Real transformer insulation oils samples of vegetable oil and mineral oil were aged by thermal cycles repeating from $30^{\circ}C$ to $120^{\circ}C$. Samples were analyzed at 42, 63, 93, 143, 190, 240, 300 cycles. The mineral and vegetable insulating oils were investigated for breakdown voltage, water content, total acid number, viscosity, volume resistivity, insulating paper and oil permittivity, and dissolved gas analyses. The breakdown voltage of the vegetable insulating oil is higher than that found for the mineral oil; the accelerated aging progress decreased the breakdown voltage. The vegetable oil had a higher water saturation than the mineral oil; the vegetable oil has the superior water characteristics and breakdown voltage. And high viscosity of vegetable oil, care has to be taken, especially when designing the cooling system for a large transformer.

Keywords

References

  1. McShane, C.P., Corkran, J., Rapp, K., Luksich, J.," Natural Ester Dielectric Fluid Development ", 2005/6 IEEE PES Transmission and Distribution Conference and Exhibition, page 18-22 (2006)
  2. 한국전기연구원, "환경친화형 식물성 변압기 절연유기술개발" (2006)
  3. IEEE std. C.57.91, "IEEE Guide for Loading Mineral Oil Immersed Transformers", (1995)
  4. COOPER Power Systems "Envirotemp FR3 fluid Testing Guide" (2004)
  5. 이병성, "植物性 絶緣油를 使用한 配電用 變壓器의 絶緣 및 冷却特性 解析, 충남대학교 대학원, (2006)
  6. 대한전기학회 전력용변압기 워킹그룹, "전력용 유입변압기 보수관리" (2004)
  7. 윤용한, 김재철, "유중가스 분석을 이용한 전력용 변압기 고장 진단 전문가 시스템" 한국조명전기설비학회 Vol.11, No.2 page 80-88 (1997)
  8. Bertrand, Y., Hoang, L.C., "Vegetal oils as substitute for mineral oils" Properties and Applications of Dielectric Materials, Vol.2 page 491-494 (2003)
  9. Rapp, K.J., Gauger, G.A., Luksich, J., "Behavior of ester dielectric fluids near the pour point", Electrical Insulation and Dielectric Phenomena, Vol.2, page 459-462, (1999) https://doi.org/10.1109/CEIDP.1999.807834
  10. Tenbohlen, S., Koch, M., " Aging Performance and Moisture Solubility of Vegetable Oils for Power Transformers", Power Delivery, IEEE Transactions on, Vol.25, page 825 - 830 (2010) https://doi.org/10.1109/TPWRD.2009.2034747

Cited by

  1. Oxidation Characteristic Changes in Insulation Oil Depending upon Storage Environments and Oil Resources vol.27, pp.5, 2016, https://doi.org/10.14478/ace.2016.1070
  2. Analysis of Insulation Characteristics for Transformer Insulating Materials According to Thermal Degradation vol.65, pp.10, 2016, https://doi.org/10.5370/KIEE.2016.65.10.1688