DOI QR코드

DOI QR Code

수동식 팽창밸브 조정에 의한 냉동시스템의 성능 분석

Performance Analysis of Refrigeration System by Adjusting Manual Expansion Valve

  • 양형석 (한국폴리텍VI대학 대구캠퍼스, 산업설비자동화과)
  • Yang, Hyung-Suk (Dept. of Automation of Industrial Installation, Korea Polytechnic VI College)
  • 투고 : 2011.05.28
  • 심사 : 2011.08.24
  • 발행 : 2011.08.31

초록

This study analyzed facts affecting the performance of refrigeration systems after throttling actions, by changing the amount of refrigerant according to adjusting the opening of manual expansion valve to 80%, or 20% with vapor compressional refrigeration training equipment. At opening of 20%, the inlet and outlet temperature of compressor, subcooling and superheat, condenser heat, refrigeration effect, flash gas heat, coefficient of performance were higher, while at 80%, condensing pressure, evaporating pressure, compression work were higher, Thus, we could see changes in the amount of refrigerant affect the performance of the refrigeration system.