Post Occupancy Evaluation for Office Building with An Underfloor Air Distribution System

바닥공조 시스템이 적용된 사무공간의 거주후 성능평가

  • 윤성훈 (한국건설기술연구원 그린빌딩연구실) ;
  • 장향인 (인하대학교 건축공학과) ;
  • 정해권 (한국건설기술연구원 그린빌딩연구실) ;
  • 최선규 (에스케이건설 건축기술본부) ;
  • 유기형 (한국건설기술연구원 그린빌딩연구실)
  • Received : 2011.10.20
  • Accepted : 2011.12.16
  • Published : 2011.12.30

Abstract

In this study, an underfloor air distribution(UFAD) system installed on the S. office building was evaluated for its indoor environmental quality performance. Field measurement and survey were conducted for the overall POE(Post Occupied Evaluation). PMV(including temperature, humidity, air velocity and globe temperature) and several environmental components were measured while thermal comfort, thermal sensation, acoustical environment and others. were investigated through survey. Except for the direct upper part of the air supply diffuser on the floor, the indoor velocity was less than 0.25m/s, which has been suggested by ASHRAES tandard 55 as the limit for thermal comfort. MRT of the perimeter zone of the room showed a higher value than that in the interior because of the introduced solar radiation through the building envelope. PMV was generally maintained in the range of thermal comfort (from -0.5 to +0.5), though it weighted to the warm side. It was reported to have 61% positive response on thermal comfort and 55% on neutral thermal sensation. The results of each survey item showed some gender-based differences. Specifically, female respondents had higher degree of dissatisfaction with indoor air cleanness and acoustical privacy. The working surface showed more than 400 lux and the equivalent noise level showed less than 50 dB(A). In conclusion, the results of the measurement and survey showed good agreement. Indoor environmental quality of the subject office room where the UFAD system was installed showed an overall excellent performance.

Keywords

References

  1. Webster, T. et al., Underfloor air distribution/Thermal stratification performance of UFAD systems, ASHRAE Journal, Vol.44, No.5, 2002.
  2. Fred S. Bauman, Underfloor Air Distribution(UFAD) Desing Guide, ASHRAE, 2003
  3. 유기형 외, 바닥공조 시스템과 천장공조 시스템의 실내환경 비교 평가, 대한건축학회논문집 계획계 20권 5호, 2004
  4. ISO 7730-2005, Ergonomics of the thermal environment - Analytical determination and interpretation of thermal comfort using calculation of the PMV and PPD indices and local thermal comfort criteria, 2005
  5. ANSI/ASHRAE Standard 55, Thermal Environmental Conditions for Human Occupancy, 1992