DOI QR코드

DOI QR Code

A Study on Estimation of Breakdown Location using UHF Sensors for Gas Insulated Transmission Lines

UHF센서를 이용한 가스절연송전선로 절연파괴 위치 추정에 관한 연구

  • Received : 2011.01.04
  • Accepted : 2011.03.22
  • Published : 2011.04.01

Abstract

This paper deals with the method and algorithm used to find fault locations in gas insulated transmission line. The method uses UHF sensors and digital oscilloscope to detect discharge signals emitted to the outside through insulating spacer in the event of breakdown inside GIL. UHF sensors are the external type and installed at outside of insulating spacers of GIL. And we used wavelet signal processing to analyze the discharge signals and confirm the exact fault location findings in the GIL test line. This method can overcome demerit of TDR(Time Domain Reflectometer) method having been applied to detect fault location for conventional underground transmission lines, and Ground Fault Sensors used in conventional GIS systems. TDR method requires high level of specialty and experience in analyzing the measured signals. Ground fault sensors are installed inside GIL and can be destroyed by high transient voltage. This paper's method can simplify the fault location process and minimize the damage of sensors. In addition, this method can estimate the fault location only by the time difference when discharge signals are arrived to detecting sensors at the ends of GIL sections without reasons of breakdown. To test the performance of our method, we installed sensors at the ends of test line of GIL(84m) and sensed discharge signals occurred in GIL, energized with AC voltage generator up to 700kV.

Keywords

References

  1. P. Coventry, M. Bues, Ph. Ponchon, A. Girodet, F. Loray, D. S. Pinches, "New generation of GIL : Characteristics and applications", B1-103, CIGRE Session 2004
  2. V. Piputvat, W. Rochanapithyakorn, T. Hillers, H. Koch, et al., "550kV Gas-Insulated Transmission Line for High Power Rating in THAILAND", B1-107, CIGRE Session 2004
  3. J. Alter, M. Ammann, W. Boeck, H. Koch et al., "N2/SF6 Gas-Insulated Line of a New GIL Generation in Service", 21-204, Session 2002, GIGRE
  4. C, K. Jung, J. B. Lee, X. H. Wang, Y. H. Song, "A Study on the Fault Location Algorithm on Underground Power Cable System", IEEE PES General Meeting, 2005
  5. C, K. Jung, J. B. Lee, "Development of Noise Cancellation Technique for Fault Location on Underground Power Cable System", KIEE Summer annual Conference, 2005. 7
  6. 장태인, 윤형희 외, "가스절연 송전선로(GIL) 장기신뢰성 시험방안 검토분석", 대한전기학회 하계학술대회 논문집, 2008.7
  7. "GIS 고장예방을 위한 UHF 부분방전 상시감시시스템 개발" 최종보고서, 산업자원부, 2006.6
  8. "지중송전 케이블시스템", 한국전력공사, 2002.12