DOI QR코드

DOI QR Code

Comparing Impact of STATCOM and SSSC on the Performance of Digital Distance Relay

  • Ghorbani, Amir (Department of Electrical Engineering, Abhar Branch, Islamic Azad University)
  • Received : 2010.12.27
  • Published : 2011.11.20

Abstract

In this paper the impact of a SSSC and a STATCOM on the impedance calculated by a distance relay is investigated. Both analytical analysis and simulations are provided. The STATCOM/SSSC control systems are modeled in detail. It is demonstrated that a SSSC has a greater impact on the calculated impedance by an A-G distance relay element. Several scenarios are considered in the simulations like the impact of the fault conditions, the compensator settings, the power system conditions and so on. All the simulations are carried out in MATLAB/Simulink with detailed models of the SSSC and the STATCOM.

Keywords

References

  1. N. G. Hingorani and L. Gyugyi, Understanding FACTS Concepts and Technology of Flexible AC Transmission Systems, New York: IEEE Press, 2000.
  2. Y. Liao and S. Elangovan, "Digital distance relaying algorithm for first-zone protection for parallel transmission lines," IEE Proc.-Gener. Transm. Distrib. Vol, 145, No. 5, pp. 531-536, Sep. 1998. https://doi.org/10.1049/ip-gtd:19982181
  3. D. L. Waikar, S. Elangovan, and A. C. Liew, "Fault impedance estimation algorithm for digital distance relaying," IEEE Trans. Power Del., Vol. 9, No. 3, pp. 1375-1383, Jul. 1994. https://doi.org/10.1109/61.311165
  4. M. Khederzadeh and T. S. Sidhu, "Impact of TCSC on the protection of transmission lines," IEEE Trans. Power Del., Vol. 21, No. 1, pp. 80-87, Jan. 2006. https://doi.org/10.1109/TPWRD.2005.858798
  5. M. Khederzadeh, A. Ghorbani, and A. Salemnia, "Impact of SSSC on the digital distance relay," IEEE/PES General Meeting, 2009.
  6. P. K. Dash, A. K. Pradhan, G. Panda, and A. C. Liew, "Digital protection of power transmission lines in the presence of series connected FACTS devise," in Proc. IEEE Power Engineering Soc. Winter Meeting, Vol. 3, pp. 1967-1972, 2000.
  7. A. Kazemi, S. Jamali, and H. shateri, "Effect of SSSC on distance relay tripping characteristic," in Proc. First International Power and Energy Conference PECon, pp. 623-628, 2006.
  8. El-Arroudi, G. Joos, and D. T. McGillis, "Operation of impedance protection relays with the STATCOM," IEEE Trans. Power Del., Vol. 17, No. 2, pp. 381-387, Apr. 2002. https://doi.org/10.1109/61.997904
  9. T. S. Sidhu, R. K. Varma, P. K. Gangadharan, F. A. Albasri and G. R. Ortiz, "Performance of distance relays on shunt - FACTS compensated transmission lines," IEEE Trans. Power Del., Vol. 20, No. 3, pp. 1837- 1845, Jul. 2005. https://doi.org/10.1109/TPWRD.2005.848641
  10. X. Zhou, H. Wang, R. K. Aggarwal, and P. Beaumont, "Performance evaluation of a distance relay as applied to a transmission system with UPFC," IEEE Trans. Power Del., Vol. 21, No. 3, pp. 1137-1147, Jul. 2006. https://doi.org/10.1109/TPWRD.2005.861329
  11. P. K. Dash, A. K. Pradhan, G. Panda, and A. C. Liew, "Adaptive relay setting for flexible AC transmission systems (FACTS)," IEEE Trans. Power Del., Vol. 15, No. 1, pp. 38-43, Jan. 2000. https://doi.org/10.1109/61.847226
  12. M. S. El-Moursi and A. M. Sharaf, "Novel controllers for the 48-pulse VSC STATCOM and SSSC for voltage regulation and reactive power compensation," IEEE Trans. Power Syst., Vol. 20, No. 4, pp. 1985-1997, Nov. 2005. https://doi.org/10.1109/TPWRS.2005.856996

Cited by

  1. Realistic insights into impedance seen by distance relays of a SSSC-compensated transmission line incorporating shunt capacitance of line vol.65, 2015, https://doi.org/10.1016/j.ijepes.2014.10.037
  2. Digital distance protection of transmission lines in the presence of SSSC vol.43, pp.1, 2012, https://doi.org/10.1016/j.ijepes.2012.05.035