Analytical Study on the Heat Transfer Characteristics of a Spirally Coiled Circular Fin-Tube Evaporator Operated Under Non-Frosting Conditions

무착상 조건에서 나선형 원형핀-튜브 증발기의 열전달 성능에 관한 해석적 연구

  • Received : 2010.03.09
  • Accepted : 2010.11.16
  • Published : 2011.02.01

Abstract

The objective of this study is to predict the heat-transfer performance of a spirally coiled circular fin-tube evaporator in which either R134a or R600a was used; this heat-transfer performance was predicted by varying the mass flow rate, inlet air temperature, air flow rate, and tube thickness. Mean deviation for the analytical model from the measured data was ${\pm}8.3%$. Simulation results revealed that at a given mass flow rate, the heat-transfer rate of the evaporator using R600a was higher than that usingR134a because the enthalpy of the former is higher than that of the latter at the given conditions. The heat-transfer rate of both refrigerants increased with an increase in the air flow rate and inlet air temperature but decreased with an increase in the tube thickness.

본 연구의 목적은 나선형 원형핀-튜브 증발기의 열전달 성능에 관하여 해석적으로 연구하는 것이다. 이를 위하여 두 가지 냉매인 R134a 와 R600a 에 대하여 냉매의 질량유량, 공기온도, 공기풍량 및 튜브직경 변화에 대하여 나선형 원형핀-튜브 증발기의 열전달 성능변화를 고찰하였다. 본 연구에서 개발된 증발기 성능해석 프로그램은 실험결과와 평균 8.3% 오차 범위 안에서 잘 예측되었다. 결과적으로, 동일한 냉매유량 범위에서 R600a 를 사용하는 경우가 R134a 를 사용하는 경우보다 더 우수한 열전달율을 나타내었다. 열전달량은 풍량 및 공기온도가 증가할수록 증가하였으나 열전달량은 튜브두께가 증가할수록 감소하였다.

Keywords

References

  1. Lee, M., Lee, H., Jang, Y. and Kim, Y., 2008, "Numerical Analysis on the Frosting Performance of a Fin-tube Evaporator Used in a Refrigerator," Trans. of the KSME, Vol. 32, No. 4, pp. 307-316.
  2. Lee, M., Kim, S. O. and Kim, Y., 2007, "Performance Evaluations of a Residential Small Multi-Refrigeration System Considering the Adiabatic Characteristics," Trans. of the KSME, Vol. 31, No. 10, pp. 868-875. https://doi.org/10.3795/KSME-B.2007.31.10.868
  3. Lee, M., Kang, T. and Kim, Y., 2010, "Air-side Heat Transfer Characteristics of Spiral-type Circular Fintube Heat Exchangers," Int. J. of Refrigeration, Vol. 33, pp. 313-320. https://doi.org/10.1016/j.ijrefrig.2009.09.019
  4. Yun, R., Kim, Y., Kim, S. and Choi, J. M., 2005, "Experimental Study on the Heat Transfer Characteristics of Spiral Fin-tube Heat Exchanger," Trans. of the SAREK, Vol. 17, No. 6, pp. 529-535.
  5. Mon, M. S. and Gross, U., 2004, "Numerical Study of Fin-spacing Effects in Annular-finned Tube Heat Exchangers," Int. J. Heat Mass Transfer, Vol. 47, pp. 1953-1964. https://doi.org/10.1016/j.ijheatmasstransfer.2003.09.034
  6. Chi, J., 1979, "A Computer Model HTPUMP for Simulation of Heat Pump Steady State Performance," NBS, Washington D.C.
  7. Domanski, P. A., 1989, "EVSIM-An Evaporator Simulation Model Accounting for Refrigerant and One Dimensional Air Distribution," NISTIR 89-4133, NIST, Washington D.C.
  8. Incropera, F. P. and Dewitt, D. P., 2003, "Fundamentals of Heat and Mass Transfer," 5th edition, John Wiley & Sons, pp. 139-477.
  9. Gunger, K. E. and Winterton, R. H. S., 1986, "A General Correlation for Flow Boiling in Tubes and Annuli," Int. J. Heat and Mass Transfer, Vol. 29, No. 3, pp. 351-358. https://doi.org/10.1016/0017-9310(86)90205-X
  10. Friedel, L., 1979, "Improved Friction Pressure Drop Correlations for Horizontal and Vertical Two-Phase Pipe Flow," European Two-Phase Flow Group Meeting, Italy, Paper E2.
  11. Kang, T., 2010, "Experimental and Analysis Study on the Heat Transfer Characteristics of a Spiral Fintube Evaporator under Non-frosting Conditions," Master Thesis, Korea University, Korea.
  12. ASHRAE Handbook, Fundamentals, 2001, "Physical Properties of Secondary Coolants (BRINES)," pp. 21.1-21.12.
  13. Lee, M., 2010, "Heat and Mass Transfer Characteristics of a Spirally-coiled Circular Fin-tube Heat Exchanger," Ph. D Thesis, Korea University, Korea.
  14. Kim, Y. and Kim, Y., 2005, "Heat Transfer Characteristics of Flat Plate Finned-tube Heat Exchangers with Large Fin Pitch," Int. J. of Refrigeration, Vol. 28, pp. 851-858. https://doi.org/10.1016/j.ijrefrig.2005.01.013