Greenhouse Cooling Using Air Duct and Integrated Fan and Pad System

일체형 팬 앤 패드 시스템과 에어 덕트를 이용한 온실 냉방

  • Nam, Sang-Woon (Department of Agricultural and Rural Engineering, Chungnam National University) ;
  • Kim, Young-Shik (Department of Plant Science and Technology, Sangmyung University)
  • 남상운 (충남대학교 지역환경토목학과) ;
  • 김영식 (상명대학교 식물산업공학과)
  • Received : 2011.07.19
  • Accepted : 2011.08.25
  • Published : 2011.09.30

Abstract

The fan and pad evaporative cooling system is one of the main cooling methods in greenhouses. Its efficiency is very high, but it has some disadvantages as temperature gradient in greenhouse is large. This study was conducted to reduce the internal temperature gradients in the fan and pad cooling greenhouses. Experiments on cooling performance were carried out in a greenhouse equipped with air duct and integrated fan and pad system as an idea of this study. It showed that the cooling efficiency of an integrated fan and pad system was 75.7% in the first stage and 88.6% in the second stage. When this cooling system was operated for an unshaded and a shaded greenhouse, there were cooling effects of $5.7\sim7.6^{\circ}C$ and $7.4\sim9.7^{\circ}C$ to the control greenhouse, respectively. Maximum temperature differences in a cooling greenhouse, with a length of 18m, were $1.6\sim1.7^{\circ}C$ for shaded conditions and $2.3\sim2.7^{\circ}C$ for unshaded conditions. This greenhouse cooling method, with air duct and integrated fan and pad system, can reduce about 40~50% of the internal temperature gradients in the usual fan and pad cooling greenhouses.

온실의 한쪽 벽에 패드를 설치하고 반대쪽 벽에 팬을 설치하여 가동하는 팬 앤 패드 냉방 온실의 온도 경사 문제를 극복하기 위한 목적으로 일체형 팬 앤패드 시스템과 에어 덕트를 설치한 온실의 냉방 실험을 통하여 냉방성능을 분석하였다. 일체형 팬 앤 패드 증발냉각기의 효율은 1단 가동시 75.7%, 2단 가동시 88.6%로 나타나 대체로 우수한 냉각효율을 보이는 것으로 판단된다. 온실의 냉방성능 실험 결과 무차광 조건에서 온실 냉방 시스템을 가동할 경우 대조구 온실에 비해서 $5.7\sim7.6^{\circ}C$ 정도의 냉방효과가 있으며 차광 조건에서는 $7.4\sim9.7^{\circ}C$ 정도의 냉방효과가 있는 것으로 나타났다. 본 시스템을 적용할 경우 여름철 온실의 최고기온을 $37^{\circ}C$ 정도로써 외기온 대비 $5^{\circ}C$ 이내로 유지할 수 있으며, 적절한 차광을 실시할 경우에는 $33^{\circ}C$ 정도에 $2^{\circ}C$ 이내로 유지하는 것이 가능하여 고온기 작물재배에 큰 도움을 줄 수 있을 것으로 생각한다. 한편, 본 냉방 실험에서 온실의 온도 분포를 분석한 결과 18m 길이의 온실 내 최대 온도 편차는 차광시 $1.6\sim1.7^{\circ}C$, 무차광시 $2.3\sim2.7^{\circ}C$ 정도로 나타났다. Kittas 등(2003)과 Nam 등(2005)의 자료와 비교한 결과 본 연구에서 구상한 일체형 팬 앤 패드 시스템과 에어 덕트를 이용한 온실 냉방시스템은 기존의 팬 앤 패드 냉방 온실의 최대 단점인 온도 편차를 40~50% 정도 개선할 수 있는 것으로 나타났다. 본 시스템은 자연환기 상태에서 가동할 수 있으므로 단동 온실에 적용하기가 쉬우며, 일체형 증발냉각기 출구로부터 온실 내 에어 덕트 시점까지의 연결 덕트 부분을 철저하게 단열하면 냉방성능을 더욱 향상시킬 수 있을 것으로 판단된다.

Keywords

References

  1. Albright, L.D. 1990. Environment control for animals and plants. ASAE. St. Joseph, Michigan. p.31-32.
  2. Arbel, A., O. Yekutieli, and M. Barak. 1999. Performance of a fog system for cooling greenhouses. J. Agric. Engng Res. 72:129-136. https://doi.org/10.1006/jaer.1998.0351
  3. Arbel, A., M. Barak, and A. Shklyar. 2003. Combination of forced ventilation and fogging systems for cooling greenhouses. Biosystems Engineering 84(1):45-55. https://doi.org/10.1016/S1537-5110(02)00216-7
  4. ASAE Standards. 1997. Heating, ventilating and cooling greenhouses. ASAE. St. Joseph, Michigan. p.663-670.
  5. Kim, M.K., K.S. Kim, and H.J. Kwon. 2001a. The cooling effect of fog cooling system as affected by air exchange rate in natural ventilation greenhouse. Journal of Bio-Environment Control 10(1):10-14 (in Korean).
  6. Kim, M.K., K.S. Kim, and S.W. Nam. 2001b. Efficient application of greenhouse cooling systems. Ministry of Agriculture and Forestry. pp.186-188 (in Korean).
  7. Kittas, C., T. Bartzanas, and A. Jaffrin. 2001. Greenhouse evaporative cooling: measurement and data analysis. Transactions of the ASAE 44: 683-689.
  8. Kittas, C., T. Bartzanas, and A. Jaffrin. 2003. Temperature gradients in a partially shaded large greenhouse equipped with evaporative cooling pads. Biosystems Engineering 85:87-94. https://doi.org/10.1016/S1537-5110(03)00018-7
  9. Lee, H.W. and Y.S. Kim. 2011. Application of low pressure fogging system for commercial tomato greenhouse cooling. Journal of Bio-Environment Control 20(1):1-7 (in Korean).
  10. Nam, S.W. 2005. Comparative analysis of evaporative cooling pad and fog systems in greenhouses. Proceeding of Bio-Environment Control 14(2):109-113 (in Korean).
  11. Nam, S.W., G.A. Giacomelli, K.S. Kim, and N. Sabeh. 2005. Analysis of temperature gradients in greenhouse equipped with fan and pad system by CFD method. Journal of Bio-Environment Control 14(2):76-82 (in Korean).
  12. Nam, S.W., W.M. Seo, Y.C. Yoon, S.K. Lee, I.B. Lee, H.W. Lee, and B.K. Cho. 2008. Bio-environment control engineering. Cheongsol Pub. Daegu. p.28-68 (in Korean).