열화된 광유와 식물성절연유에서 온도, 벤조트리아졸의 유동대전 영향

Influence of Temperature and Benzotriazole on the Flow Electrification by aging Mineral, Vegetable Oil

  • 투고 : 2010.09.30
  • 심사 : 2010.12.27
  • 발행 : 2011.02.01

초록

In this paper, the FT-IR, conductivity and flow electrification phenomena of Vegetable oils were discussed. Vegetable oil has high flash point and eco-friendly properties compared to conventional mineral oil. Accelerated aging transformer oil samples produced in the oven at 140[$^{\circ}C$] for 500 hours, 1000 hours, 1500 hours, 2000 hours. Serial device to measure the flow electrification phenomena was designed and fabricated. Pico ammeter and the Labview data measurements were utilized. The effects of Temperature and antistatic agent on fluid flow electrification were investigated. Both Mineral and vegetable oil showed similar trends for temperature change. The polarity reversal occurred in mineral oil with antistatic agent above 10 ~ 30[ppm] and in vegetable oil with antistatic agent above 5[ppm].

키워드

참고문헌

  1. Hiroyoshi Kitabayashi, Kosei Tsuji and Keiichi Itoh, "A streaming electrification model based on differences of work function between solid materials and insulating oil", Journal of Electrostatics 63, 735-741, 2005. https://doi.org/10.1016/j.elstat.2005.03.037
  2. H.Wu and S.Jayaram, "dc Field Effects on Streaming Electrification in Insulating Oils" IEEE, Vol.3, No.4, August 1996.
  3. Moreau, E., Paillat, T., Touchard, G., "Flow electrification in high power transformers: BTA effect on pressboard degraded by electrical discharges", Dielectrics and Electrical Insulation, IEEE, Vol.10 15 - 21, 2003. https://doi.org/10.1109/TDEI.2003.1176551
  4. IEEE Std. C.57.91, "IEEE Guide for Loading Mineral Oil Immersed Transformer" IEEE,Inc., 1995.
  5. Rapp, K.J, McShane, C.P., Luksich, J., "Interaction mechanisms of natural ester dielectric fluid and Kraft paper ", IEEE International Conference on Dielectric Liquids, 393-396, 2005.
  6. S. ltahashi, et al., "Analysis of Water Oil-impregnated Kraft Paper and its Effect on Conductivity", IEEE Transactions on Dielectrics and Electrical Insulation Vol.2 No.6, 1111-1116.
  7. Washabaugh, A.P., Zahn, M., "Flow electrification measurements of transformer insulation using a Couette flow facility", Dielectrics and Electrical Insulation, IEEE, Vol. 3, 161 - 181, 1996. https://doi.org/10.1109/94.486767
  8. Ieda, M. et al., "Suppression of static electrification of insulating oil for large power transformers", Electrical Insulation, IEEE, vol.23 153-157, 1988. https://doi.org/10.1109/14.2349