Additional Improvement and Evaluation of Exhaust Ventilation Systems at Small and Medium Sized Enterprise

중.소규모 사업장의 국소배기장치 설치 실태와 문제점 및 개선방안

  • Lim, Seong-Keun (Center of ChungBuk Industrial Health, Korean Industrial Health Association) ;
  • Park, Doo-Yong (Occupational Safety and Health Research Institute, Korea Occupational Safety and Health Agency) ;
  • Kim, Won-Ki (WiseH) ;
  • Kim, Soo-Geun (Dept. of Occupational Medicine, Kangbuk Samsung Hospital Sungkyunkwan University School of Medicine)
  • 임성근 (대한산업보건협회 충북산업보건센터) ;
  • 박두용 (한국산업안전공단 산업안전보건연구원) ;
  • 김원기 (와이즈에이치) ;
  • 김수근 (성균관대학교 의과대학 산업의학교실 강북삼성병원 산업의학과)
  • Received : 2008.01.17
  • Accepted : 2009.12.17
  • Published : 2010.03.30

Abstract

Objectives : The purposes of this study were to evaluate exhaust ventilation systems(EVSs) and to suggest problems and improvements. Methods : For 50 small and medium-sized enterprises, we carried out evaluation of EVSs. We evaluated hoods with smoke tester and measurement of capture velocity. In addition, we used several indicators for performance evaluation designed in this study. Results : 1. Based on the smoke flow pattern and the criteria of occupational health and safety act, 67.8% of hoods were rated 'good' level at smoke test whereas 26.3% were rated 'good' level at measurement of capture velocity. 2. 29.3% of hoods, of which ratio of measured actual air flow at hood(Qah) to required ideal exhaust air flow at hood(Qih) was 1 or more, were rated 'good' level. 3. The % of EVS, of which ratio of measured actual air flow at stack(Qast) to total required ideal exhaust air flow at hood(Qith) was 1 or more, was 29.0%. 4. For the ratio of measured Qast to existing air flow at fan(Qfan), only 5% of EVSs were 1 or more and 26.0% were 0.8 or more but less than 1.0. 5. For the ratio of measured Qast to total measured actual exhaust air flow at hood(Qath), 74.0% were 0.8 or more but less than 1.0. 6. The percentage of EVS, of which ratio of total measured Qath to existing Qfan was 0.8 or more, was 19.0%. 7. The percentage of EVS, of which ratio of total measured Qath to total required ideal exhaust Qith was 1 or more, was 26.0%. 8. For the comprehensive evaluation indicators designed in this study, 29.0% were 0.8 or more. Conclusions : We found that few exhaust local ventilations at small and medium-sized enterprises were rated 'good' level and that most exhaust local ventilations had 'poor' design and installation. Therefore, relevant professional manpower and enterprises have to construct exhaust local ventilation where it is needed, and technical guidance and economic support are needed to improve 'poor' exhaust local ventilation after self-evaluation.

Keywords

References

  1. 김태형,하현철. 사업장 국소배기장치 관리 및 성능향상을 위한 제도개선 연구. 한국산업안전공단 산업안전보건연구원. 2005.
  2. 노동부. 산업보건기준에 관한규칙. 2006.
  3. 박선근. 사업장내 국소배기설비의 점검과 개선방안에 관한 연구. 인천대학교. 2005.
  4. 박성기,정경동,김두희. 국소배기장치 유무에 따른 용접흄 폭로량. 대한산업의학회지 1993;5(1);p.163-169.
  5. 서은홍. 자체검사 항목. 검사방법 및 평가기준의 개선 연구. 한국산업안전공단 안전공학연구실. 2005.
  6. 윤영노, 이경용. 사업장의 국소배기 설비와 관련된 정보수집 연락망에 대한 연구. 한국산업위생학회지 2000;10(2):p.1-17.
  7. 이필용. 울산지역 소규모 사업장에 대한 공정별 국소배기장치의 점검과 개선방안. 인제대학교. 2001.
  8. 최우호. 국소배기장치의 제어속도 측정시 오차. 2000.
  9. 한국산업안전공단 국소배기장치 실태조사 보고서; 1991.
  10. 한돈희. 산업환기공학. 신광출판사;2001.
  11. ACGIH. INDUSTRIAL VENTILATION A Manual of Recommended Practice 15th Edition; 2004