Abstract

Ground-source(Geothermal) heat pump(GSHP) systems can achieve a higher coefficient of performance than conventional air-source heat pump(ASHP) systems. However, GSHP systems are not widespread because of their expensive installation costs. The authors have developed a GSHP system that employs the cast-in-place concrete pile foundations of a building as heat exchangers in order to reduce the initial cost. In this system, eight U-tubes are arranged around the surface of a cast-in-place concrete pile foundation. The heat exchange capability of this system, subterranean temperature changes and heat pump performance were investigated in a full-scale experiment. As a result, the average values for heat rejection were 186~201 W/m(per pile, 25 W/m per pair of tubes) while cooling. The average COP of this system was 4.6 while cooling; rendering this system more effective in energy saving terms than the typical ASHP systems.

Keywords

References

  1. Lee, J. Y., 2009, Current status of ground heat pump in Korea, Renewable and Sustainable Energy Reviews, Vol. 13, pp. 1560-1568. https://doi.org/10.1016/j.rser.2008.10.005
  2. Baek, S. K. et al., 2007, Development of Ground Heat Exchangers installed in Builindg Foundation, Proceedings of the SAREK 2007 Summer Annual Conference, pp. 277-282.
  3. Yu, H. K., 2008, Development and Performance Evaluation of Ground Heat Exchanger Uilizing PHC Pile Foundation of Building, Journal of the Korean Solar Energy Society, Vol. 28, No. 5, pp. 56-64.
  4. Nagano, K. and Ochifuji, K., A study on the ground coupled heat pump system(Part 1-Part 4), 1994-1996, Transaction of Society of Heating, Air-Conditioning and Sanitary Engineers of Japan.
  5. Morino, K. and Oka, T., 1989, Experimental and numerical study of exchanged heat in soil by circulating water in a steel pile, Journal of Environmental Engineering(Transactions of AIJ), pp. 49-57.
  6. Kavanaugh, S. P., 1992, Field Test of a Vertical Ground-Coupled Heat Pump in Alabama, ASHRAE Transactions, Vol. 98, No. 2, pp. 607- 615.