Evaluation on the Solar Heat Gain Coefficient of Glazing System installed in internal shading device by experiments according to the NFRC 201

NFRC 201 실험방법에 의한 내부 차양장치가 적용된 창호의 일사획득계수 평가

  • Lim, Jae-Han (Dept. of Architectural Engineering, Ewha Womans University) ;
  • Song, Seung-Yeong (Dept. of Architectural Engineering, Ewha Womans University)
  • 임재한 (이화여자대학교 건축공학과) ;
  • 송승영 (이화여자대학교 건축공학과)
  • Received : 2010.04.21
  • Accepted : 2010.05.24
  • Published : 2010.06.30

Abstract

Recently the researchers has been interested in the development of the high performance windows such as solar control window using automatic shading devices, air-flow window, selective coating window. In order to assess the energy performance of total fenestration system, the net energy gains or losses through the glazings and windows should be evaluated. It depends on the thermal transmittance (U-value) and the total solar energy transmittance (SHGC, g-value). This study aims to measure the solar heat gain coefficient according to the NFRC 201 standard test method. In results, we could find the result of different SHGC of the glazing system with a different slat angles. The SHGC in case of $90^{\circ}$ of internal slat angle with regard to the window surface is about 0.56, that in case of $45^{\circ}$ is about 0.49 and that in case of $0^{\circ}$ is about 0.33. Significant dependence on the solar radiation intensity and incident angle was found in comparison of the measured and simulated SHGC.

Keywords

References

  1. T.R. Nielsen, K. Duer and S. Svendsen, Energy performance of glazing and windows, Solar energy, Vol 69, pp. 137-143.
  2. 기술표준원, KSF 2278 창호의 단열성 시험 방법, 2008.
  3. 기술표준원, KSF 2277 건축용 구성재의 단열성능 측정방법 - 교정 열상자법 및 보호 열상자법, 2007.
  4. 기술표준원, KSF 2824 차양의 일사 차폐 계수 간이 시험 방법, 2006.
  5. 구혜연 외, 하절기 베네시안 블라인드의 자동 제어 방안에 관한 연구, 대한건축학회 학술발표대회논문집, 27권 1호, 2007. 10, pp. 889-892.
  6. 열조창호연구단, www.heatwindow.kr
  7. 윤종호 외, 창호의 일사획득성능 측정장치 개발 연구, 공기조화냉동공학회 97 하계학술발표회 논문집 , 1997, pp. 648-653.
  8. 김기세 외, 태양열 획득계수 측정장치 Solar Calorimeter 개발, 한국태양에너지학회 추계 학술대회논문집, 1997, .pp 89-95.
  9. Hans Simmer, Bruno Binder, Experimental and numerical deterrnination of the total solar energy transmitt -ance of glazing with venetian blind shading, Building and Environment 43, 2008, pp. 197-204. https://doi.org/10.1016/j.buildenv.2006.10.011
  10. ISO, ISO 15099 Thermal performance of windows, doors and shading devices - Detailed calculations, 2003
  11. www.nfrc.org
  12. NFRC(National Fenestration Rating Council), NFRC 201 Interim standard test method for measuring the solar heat gain coefficient of fenestration systems using calorimetry hot box methods, 2003.
  13. ASHRAE, 2005 ASHRAE Handbook-Fundamentals ch. 31 Fenestration, 2005.
  14. J.H. Klems, Warner and G.O. Kelley, A comparison between calculated and measured SHGC for complex fenestration systems, ASHRAE Winter meeting, 1996, pp. 17-21.