DOI QR코드

DOI QR Code

PROTECTION SEQUENCE OF AC/DC CONVERTERS FOR ITER PF MAGNET COILS

  • Received : 2009.09.11
  • Accepted : 2010.03.24
  • Published : 2010.06.30

Abstract

The protection sequence of an AC/DC converter for an ITER PF coil system is developed in this study. Possible faults in the coil system are simulated and the results reflected in the design of a sequence to protect the coil and converter. The inductances of the current sharing reactors and thyristor numbers in parallel with the bridge arms are optimized with the designed protection sequence.

Keywords

References

  1. Design Description Document for the ITER Pulsed Power Supply System, DDD4.1 (2001) ITER Office
  2. Roshal A. et al., "Status of ITER Coil Power Supply Design" in Proc. of the EPIR-6 Conference, 1997, St. Petersburg, RF.
  3. Benfatto I. et al., "AC/DC Converters for the ITER Poloidal System" in Proc. of the 16th SOFE, 1995, Champaign, IL, USA, pp. 658-661
  4. E. Gaio, R. Piovan, V. Toigo, I. Benffato, "Bypass Operation of the ITER AC/DC Converters for Reactive Power Reduction" presented at the 17th SOFE, San Diego, CA, USA, 1997
  5. ABB Semiconductors, Doc. No. 5SYA 1050-02 May 07

Cited by

  1. Operation modes and Protection of VS(Vertical Stabilization) Converter for International Thermonuclear Experimental Reactor vol.20, pp.2, 2015, https://doi.org/10.6113/TKPE.2015.20.2.130