DOI QR코드

DOI QR Code

중성점 접지 리액터 주변 작업자의 인체내부 유도전류밀도 특성

Characteristics of the Current Density Induced Inside a Worker Near a Neutral Ground Reactor

  • 민석원 (순천향대 공대 전기통신공학과) ;
  • 이승호 (순천향대 대학원 전기통신공학과)
  • 투고 : 2010.07.29
  • 심사 : 2010.08.30
  • 발행 : 2010.10.01

초록

To reduce a high fault current, neutral ground reactors (NGR) were installed in the Korean substation. Current with several harmonic components flows in a NGR due to load unbalance in normal steady state and magnetic fields with several harmonic components are also generated around a NGR. As results of study, we found magnetic fields around a NGR in Korean substation included two harmonics, 180Hz and 540Hz. Magnetic fields of 180 Hz increased 3 times more current density inside a worker near a NGR than same magnitude magnetic fields of 60 Hz. We know a worker near a NGR may not meet ICNIRP guideline of 10(mA/$m^2$) due to several harmonic components.

키워드

참고문헌

  1. 장종근, 김정부, "전력용 변압기 고장전류 감소를 위한 중성점 리액터 적용 연구," 대한전기학회 1990년도 추계학술대회 논문집, pp.210-213, 1990년 11월.
  2. 박희철 외, "배전계통의 고조파에 의한 NGR의 문제점에 관한 연구," 대한전기학회 2004년도 하계학술대회논문집 A, pp.480-482, 2004년 7월.
  3. P. A. Demers, D. B. Thomas, A. Sternhagen, W. D. Thompson, M. G. Curnen, W. Satariano, D. F. Austine, P. Issacson, R. S. Greenberg, C. Key, L. K. Kolonel, D. W. West, "Occupational exposure to electromagnetic fields and breast cancer in men," Am. J. Epidemiol., vol. 132, pp. 775-776, 1991.
  4. G. Theriault, M.Goldberg, A. B. Miller, B. Armstrong, P. Guenel, J. Deadman, E. Imbernon, T. To, A. Chevalier, D. Cyr, C. Wall, "Cancer risks associated with occupational exposure to magnetic fields among electric utility workers in Ontario and Quebec, Canada, and France-1970-1989," Am. J. Epidemiol., vol. 139, pp. 550-572, 1994. https://doi.org/10.1093/oxfordjournals.aje.a117046
  5. D. A. Savitz, D. P. Loomis, "Magnetic field exposure in relation to leukaemia and brain cancer mortality among electric utility workers," Am. J. Epidemiol., vol. 141, pp. 123-134, 1995. https://doi.org/10.1093/oxfordjournals.aje.a117400
  6. International Commission on Non-Ionizing Radiation Protection, "Guidelines for limiting exposure to time-varying electric, magnetic, and electromagnetic fields (up to 300GHz)," Health Phys., vol. 74, pp. 494-522, April 1998.
  7. P. J. Dimbylow, "Induced current densities from low-frequency magnetic fields in a 2 mm resolution, anatomically realistic model of body," Phys. Med. Biol., vol. 43, pp. 221-230, 1998. https://doi.org/10.1088/0031-9155/43/2/001
  8. C. M. Furse, O. P. Gandhi, "Calculation of electric fields and currents induced in a millimeter resolution human model at 60 Hz using the FDTD method," Bioelectromagnetics, vol. 19, pp. 293-299, 1998. https://doi.org/10.1002/(SICI)1521-186X(1998)19:5<293::AID-BEM3>3.0.CO;2-X
  9. P. Baraton, J. Cahouet, B. Hutzler, "Three dimensional computation of the electric fields induced in a human body by magnetic fields," in Proc. of 8th Intern. Symposium on High Voltage Engineering 1993, pp. 517-520.
  10. O. Bottauscio, R. Conti, "Magnetically and electrically induced currents in human body models by ELF electromagnetic fields," in Proc. of 10th Intern. Symposium on High Voltage Engineering 1997, 5-8.
  11. K. Yamazaki, T. Kawamoto, H. Fujinami, T. Shigemitsu, "Investigation of ELF magnetically induced current inside human body development of estimation tools and effect of organ conductivity," Trans. IEE Japan, vol. 120-A, pp. 81-87, Jan. 2000.
  12. P. J. Dimbylow, "Induced current densities from low - frequency magnetic fields in a 2 mm resolution, anatomically realistic model of the body," Phys. Med. Biol., vol. 43, pp. 221-230, 1998. https://doi.org/10.1088/0031-9155/43/2/001
  13. P. Baraton, et al., "Three dimensional computation of the electric fields induced in a human body by magnetic fields," Proc. of 8th Intern. Symp. on High Volt. Eng., pp. 517-520, 1993.
  14. P. Baraton, et al., "Magnetically induced currents in the human body," IEC Technology Trend Assessment, 1995.