Abstract

The development of overload management systems for distribution transformers offers new opportunities for improving the reliability of distribution systems. It allows network planners to optimize the system resource utilization and investment cost. Such an improvement in the flexibility of the distribution network is only possible if the operator has more accurate knowledge of the realtime conditions of distribution transformers. In this paper, we present an improved overload decision system for distribution transformers using realtime monitoring data. Our study can be categorized into two parts: (a) improvement in the criteria for judging the overload conditions of distribution transformers and (b) development of an overload evaluation system using realtime monitoring data. In order to determine the overload criteria, overload experiments are performed on sample transformers; the results of these experiments are used to define the relationship between the transformer overload and the increase in the top-oil temperature. To verify the accuracy of the experimental results, field tests are performed using specially manufactured transformers, the loads and top-oil temperatures of which can be measured. For arriving at online overload decisions, we propose methods whereby the measured load curve can be converted into an overload characteristic curve and the overload time can be calculated for any load condition. The developed system is able to evaluate the overload for individual distribution transformers and calculate the losses using realtime monitoring data.

Keywords

References

  1. 박창호 외, 주상변압기 부하관리 개선에 관한 연구 (최종보고서), 한국전력공사, 1999년.
  2. J. A. Jardini, H. P. Schmidt, C. M. V. Tahan, C. C. B. De Oliveira, and S. U. Ahn, "Distribution transformer loss of life evaluation: a novel approach based on daily load profiles," IEEE Trans. on PWRD, vol. 15, no. 1, pp. 361-366, Jan. 2000.
  3. J. A. Jardini, C. M. V. Tahan, S. U. Ahn, and E. L. Ferrari, "Distribution transformer loading evaluation based on load profiles measurements," IEEE Trans. on PWRD, vol. 12, no. 4, pp. 1766-1770, Oct. 1997.
  4. A. Sargent, R. P. Broadwater, J. C. Thompson, and J. Nazarko, "Estimation of diversity and kWh-topeak- kW factors from load research data," IEEE Trans. on PWRS, vol. 9, no. 3, pp. 1450-1456, Aug. 1994.
  5. R. P. Broadwater, A. Sargent, A. Yarali, H. E. Shaalan, and J. Nazarko, "Estimating substation peaks from load research data," IEEE Trans. on PWRD, vol. 12, no. 1, pp. 451-456, Jan. 1997.
  6. S.-Y. Yun, J.-C. Kim, and C.-H. Park, "Peak load estimation of pole-transformer using load regression equation and assumption of cooling load for customer," Int. Jr. of EPES, vol. 24, no. 9, pp. 743-749, Nov. 2002.
  7. 박창호, 배전용 변압기 최적 부하관리 방안 연구 (TR), 한국전력공사 전력연구원, 2003년.
  8. 한국전력공사 배전처, 저압부하관리 업무편람, 한국전력공사, 1999년 5월.
  9. 한국전기연구소 전력시험부, '99 변압기 실무기술, 한국전기연구소, 1999년 6월.
  10. 윤상윤, 김재철, 박창호, "최상부 유온 상승 특성을 이용한 100kVA 이하 유입식 배전용 변압기의 과부하 판정 기준," 대한전기학회 논문지, 제 51A권, 제 11호, pp. 559-567, 2002년 11월.