Abstract
HVDC is better economic method than HVAC in case of long distance transmission and it is possible to interconnect transmission lines regardless of difference of power frequency. The electrical environment problems of HVDC overhead transmission line are electric field, charged voltage, ion current and so on. For biopolar HVDC lines, most of the ions are directed toward the opposite polarity conductor, but a significant fraction is also directed toward the ground. These problems are major factor to design configuration of HVDC overhead transmission line. Therefore, It is necessary to test an environmental characteristics of HVDC overhead transmission line. In this paper, to assess the ion characteristic of HVDC transmission line, continuous measurements have been done on the biopolar single circuit line with ACSR 480mm2-6 bundle conductors of Gochang HVDC Test line. And then the ion characteristics were analyzed.