Abstract
When small scale wind and solar power generation systems are connected to conventional power distribution system. It is worried that it can affect the quality of electricity such as voltage variation, power factor, frequency, harmonics and flicker. Therefore, in this research, in order to investigate the effects of wind power generation equipments(AC link method) on electrical power quality, when they are connected to distribution system. Power quality analyzer was installed respectively at the front side of power conversion system of conventional wind generation system and secondary side of consumer's power supply at distribution line. Measurements on power quality were performed and the effects of the wind generation system on distribution system were analyzed when it was and was not operated. The results show that 0.34[%] increase on voltage variation, 0.145 increase on current crest factor and 0.6[$^{\circ}$] deviation on phase difference when the power generation system was operated.
소규모 풍력 및 태양광설비가 기존의 배전계통에 연계되어 전압변동, 역률, 주파수, 고조파, 플리커 등의 전원품질 요소에 영향을 줄 것으로 우려하고 있다. 따라서 본 연구에서는 풍력발전설비(AC 링크방식)가 연계된 배전계통의 전력품질에 어떠한 영향을 줄 수 있는지에 대한 조사를 위하여 현재 운영 중에 있는 풍력발전설비의 전력변환장치 앞과 배전선로측 수용가 전원설비 2차측에 각각 전력품질 분석 장치를 설치하여 실측하고 풍력발전기가 가동과 정지 상태에서 배전선로측에 어떠한 영향을 주는지에 대하여 분석하였다. 분석결과 발전기가 가동 및 정지 시 전압변동이 0.34[%] 상승, 전류파형파고율 0.145 정도 상승, 위상차가 가동 중일 때 0.6[$^{\circ}$] 정도의 편차를 발생시켰다.