DOI QR코드

DOI QR Code

Load Shedding Schemes of Under Frequency Relay to Improve Reliability in Power Systems

전력계통 신뢰도 강화를 위한 저주파계전기의 적정 부하차단 방안

  • Received : 2010.05.29
  • Accepted : 2010.06.07
  • Published : 2010.07.01

Abstract

This paper proposes an efficient under frequency relay load shedding scheme for the korea power system which is more than two times than the system size and its capacity of the power system 10 years ago. The proposed method is keeping the power system stability and supports for the operating system during critical situations such as big disturbances and unstable in supply and demand. In order to determine the number of load shedding steps, the load to be shed per step, and frequency level, it is necessary to investigate and analyze maximum losses of generation due to the biggest contingency, maximum system overload, maximum keeping frequency, maximum load to be shed, and recovery frequency. The proposed method is applied to Off-peak load(25,400MW) and Peak load(62,290MW) of Korea Electric Power Corporation to demonstrate its effectiveness.

Keywords

References

  1. 한국전력거래소, "저주파계전기에 의한 적정 부하차단 방식에 관한 연구", 2008
  2. 제 3 차 전력수급 기본계회(산업자원부 고시, 2006. 12)
  3. GE 보고서, "Load Shedding, Load Restoration and Generator Protection Using Solid-state and Electromechanical Underfrequency Relays", GET-6449
  4. 호주 저주파 부하차단 보고서, "NEMMCO Operating Procedure"
  5. WECC 저주파 부하차단 보고서, "WECC-ONF-Report", July, 2005
  6. 한국전력공사, "전력계통운용자료집", 1996 계통운용처 pp.170
  7. 정봉상, 전영환, 김일동, 양정재, "우리나라 계통의 주파수응답특성에 의한 발전기정수 산정에 관한 연구", 대한전기학회 논문지, 제58권, 제4호, pp.688-693, 2009