Abstract

The inundation of substation and ground power equipment breaks out every summer season in low-lying downtown areas and low-lying shores by torrential rain, typhoons and tsunamis. It has, in turn, caused replacement, social and economic costs for blackouts. For activity management regarding flood damage we produced a flood protection system which using the Pad transformer as a basic frame and is developed using pneumatic pressure. We tested safety concerns including insulation resistance and current leakage first for water tank flooding and, second, by an empirical test through supplying 22.9[kV]. We estimate that costs associated with flooding and power failure can be diminished by these advances toward creating a more reliable system.

Keywords

References

  1. Korea enviroment Institute reseach, “Sea Level Rise and its Possible Impact near the Korea due to Global Warming II”, Report, 2002. 12.
  2. KEPCO,“2006 Distribution Supply Equipment Power Failure Analytical and Preventive Countermeasure”, Report 2007. 4
  3. KEPCO, “Korea Electric Power Corporation Standard Purchase Specifications (Pad Transformer), 2001. 6.
  4. Jae-Yong , Lee et 8, “The Development of Inundation Prevention Apparatus for Electric Power Equipment in Flood Area”, Final Report, Yeungnam College of Science & Technology, 2009. 2.
  5. Gi-Hyun, Kim et 3, “The Development of Flood Protection System for Pad Transformer using Pneumatic pressure”, KIEE Vol.58P, No. 1, MAR., pp.90-94, 2009.
  6. Ministry of knowledge Economy, “The Korea Electric Power Industry Codes and Standards and , 2010. 1.