DOI QR코드

DOI QR Code

Analysis of the Ground Surface Potential Rise using a Hemisphere-Shaped Test Model

반구형 실험모델을 이용한 대지표면 전위상승의 분석

  • 유재덕 (인하대 대학원 전기공학과) ;
  • 조용승 (인하대 대학원 전기공학과) ;
  • 이복희 (인하대학교 IT공대 전기공학부)
  • Received : 2010.10.28
  • Accepted : 2010.11.16
  • Published : 2010.12.31

Abstract

This paper deal with an analysis of the ground surface potential profiles using a hemispherical scaled-model. Because it is very difficult to draw valid conclusions concerning a general grounding problem from actual field data, scale model tests can be used to determine the ground surface potential profile around the grounding electrodes according to the configuration of grounding electrodes. In this work, a hemispherical vessel with a diameter of 1,100 [mm] was employed to simulate uniform soil and CDEGS program was employed to compare the measured and simulated results. As a result, the ground surface potential around the grounding electrode was significantly raised and the ground surface potential at the just upper point of ground electrode particularly was higher than other points. The ground surface potential of counterpoise was higher than other grounding electrodes such as mesh and grounding rods and the ground surface potential strongly depends on the frequency responses of grounding electrodes. Also the results measured with the small-sized model were in reasonably agreement with the data obtained from simulation.

Keywords

References

  1. 이복희, 이승칠 , 접지의 핵심 기초기술 제 2판, (주)의제전기설비연구원, pp. 69,1999.
  2. R Kosztaluk, M. Loboda, D. Mukhedkar, “Experimental Study of Transient Ground Impedances.”, IEEE Tras. PAS, Vol.100, No.11, pp.4653-4660, 1981. https://doi.org/10.1109/TPAS.1981.316807
  3. 백영환, 이복희, “축소형 모델 접지전극의 매설깊이에 따른 위험전압의 분석”, 한국 조명.전기설비학회논문지 제23권 제4호, p.p 107, 2009.4. https://doi.org/10.5207/JIEIE.2009.23.4.056
  4. 배성배, 최종혁, 박건훈, 이복희, “대지저항률에 따른 접지임피던스의 주파수 의존성”, 한국조명.전기설비학회 2008 춘계학술대회 논문집, p.p 464, 2008.5.
  5. H. B. Dwight, “Calculation of Resistance to Ground.”, Electrical Eng. Vol. 55, pp.1319, 1936. https://doi.org/10.1109/EE.1936.6539232
  6. 김태기, 최영철, 최종혁, 이복희, “대지저항률에 따른 매설지선의 접지임피던스의 주파수의존성”, 조명.전기설비학회논문지 제24권 제5호, p.p 168, 2010.5. https://doi.org/10.5207/JIEIE.2010.24.5.114
  7. 정현욱, “배전용 전주 주변에서 접촉전압과 보폭전압의 분석”, 인하대학교 석사 학위논문, 2006.8.