DOI QR코드

DOI QR Code

누전차단기 실태조사 및 교체주기에 관한 연구

A Study on the Real Condition and Life Time of the RCD

  • 투고 : 2010.08.30
  • 심사 : 2010.09.29
  • 발행 : 2010.12.01

초록

In this study, an analysis of the used RCD's condition is conducted to assess the effect on environment of installation area, terms of use, corrosion, contamination etc. According to KS C 4613, the used RCDs were tested to get date which is the RCD's life time. And then, the date is analysed using Minitab which is a statistical program for reliability analysis. As a result, The RCD's MTTF for the all samples is $12.7{\pm}0.23$ years. and the MTTF of RCDs which are used indoor area is $12.9{\pm}0.34$ years, the MTTF of RCDs which are used outdoor area is $11.9{\pm}0.30$ years. Futhermore, the MTTF of RCDs which are used in dry area is a $13.1{\pm}0.26$ years, the MTTF of RCDs which are used in dust area is $13.0{\pm}0.57$ years, the MTTF of RCDs which are used in moisture area is $8.4{\pm}0.77$ years.

키워드

참고문헌

  1. M. Capelli-Schellpfeffer, M. Toner, "Advances in the Evauluation and Treatment of Electrical and Thermal Injury Emergencies", IEEE Trans, Ind. appl., Vol.31, No.5, pp.1147-52, 1995 https://doi.org/10.1109/28.464531
  2. 이재복 외 4명, "누전차단기의 뇌써지 동작특성 분석 및 오동작 대책", 2002 KIEE Vol. 5, No. 10, pp.479-484, 2002.
  3. 유재근, 이상익, 전정채, "자가용 수용가에서 배선용 및 누전차단기 오동작에 대한 조사연구", Journal of KIIEE, Vol. 19, No. 2, pp.87-93, 2005. 03.
  4. 한국전기안전공사, "전기재해통계분석", 제18호, 2009. 12.
  5. 김언석, 한윤탁, 김봉성, 정종일, 정병하, 김재철, "누전 차단기의 충격파 부독작 특성과 EMC 성능 비교분석", 2003 KIIEE 추계학술논문집, pp.319-323, 2003. 11.
  6. 이복희, 이승칠, 김찬오, "뇌임펄스전압에 대한 30[A]용 고감도형 누전차단기의 오동작에 대한 특성의 해석", Journal of KIIEE Vol. 11, No. 6, pp.96-103, 1997. 11.
  7. KS C 4613, "누전차단기", 기술표준원, 2009.
  8. KS C IEC 61009-1, "가정용 및 이와 유사한 설비의 과전류 보호용 누전 차단기", 기술표준원, 2002.
  9. 서순근, "Minitab 신뢰성 분석", 이레테크, 2009. 2.