DOI QR코드

DOI QR Code

HTS SMES Application Simulation for Power Quality Simulation

전력품질 개선을 위한 HTS SMES 적용 시뮬레이션

  • 김아롱 (창원대 공대 전기공학과) ;
  • 김경훈 (창원대 공대 전기공학과) ;
  • 김진근 (창원대 공대 전기공학과) ;
  • 박민원 (창원대 공대 전기공학과) ;
  • 유인근 (창원대 공대 전기공학과) ;
  • 이상진 (위덕대 공대 에너지전기공학부) ;
  • 박정도 (위덕대 공대 에너지전기공학부) ;
  • 이동영 (위덕대 공대 에너지전기공학부)
  • Received : 2010.09.13
  • Accepted : 2010.10.28
  • Published : 2010.12.01

Abstract

Wind power generation system (WPGS) of Ulleung Island causes frequency and voltage fluctuation due to wind speed variation during night time. Superconducting magnetic energy storage (SMES) system can overcome the fluctuations through the fast response time of energy charging and discharging. The SMES system should be connected to the terminal of the WPGS for frequency stabilization. To demonstrated the effectiveness of SMES system for power quality improvement, Ulleung Island power network was modeled in a real time digital simulator (RTDS). The RTDS-based simulation results of power quality improvement with SMES are investigated and discussed in detail.

Keywords

References

  1. H.Y. Jung, A.R. Kim, J.H. Kim, M. Park, I.K. Yu, S.H. Kim, K. Sim, H.J. Kim, and K.C. Seong, T. Asao and J. Tamura, "A study on the operating characteristics of SMES for the dispersed power generation system," IEEE Trans. Appl. Supercond., vol.19, no.3 pp.2028-2031, Jun. 2009. https://doi.org/10.1109/TASC.2009.2018495
  2. A.R. Kim, H.R. Seo, G.H. Kim, M. Park, I.K. Yu, Y. Otsuki, J. Tamura, S.H. Kim, K. Sim, and K.C. Seong, "Operating characteristic analysis of HTS SMES for frequency stabilization of dispersed power generation system," IEEE Trans. Appl. Supercond., vol. 20, no. 3, pp. 1334-1338, Jun. 2010. https://doi.org/10.1109/TASC.2010.2044164
  3. Z. Lubosny, "Wind Turbine Operation in Electric Power Systems," Springer–Verlag Berlin Heidelberg, 1st ed, Zbigniew Lubosny, pp. 132-162, 2003.
  4. A.R. Kim, G.H. Kim, K.M. Kim, J.G. Kim, D.W. Kim, M. Park, I.K. Yu, S.H. Kim, K. Sim, and K.C. Seong, "Design and manufacturing of a SMES model coil for real time digital simulator based power M. Park, I.K. Yu, S.H. Kim, K. Sim, and K.C. Seong, "Design and manufacturing of a SMES model coil for real time digital simulator based power quality enhancement simulation," IEEE Trans. Appl. Supercond., vol. 20, no. 3, pp. 1339-1343, Jun. 2010. https://doi.org/10.1109/TASC.2009.2039788
  5. T. Asao, R. Takahashi, T. Murata, J. Tamura, M. Kubo, Y. Matsumura, A. Kuwayama, and T. Matsumoto "Evaluation method of power rating and energy capacity of Superconducting Magnetic Energy Storage system for output smoothing control of wind farm," Electrical Machines and systems, ICEMS, vol.8, pp.302-307, 2007.
  6. H.K. Yeom, S.J. Park, Y.J. Hong, D.Y. Kho, K.C. Seong, H.J. Kim and T.B. Seo, "An experiment study of the conduction cooling system for the 600kJ HTS SMES," IEEE Trans. Appl. Supercond., vol.18, no.2, pp.741-744, Jun. 2008. https://doi.org/10.1109/TASC.2008.921217
  7. P. Tixador, M. Deleglise, A. Badel, K. Berger, B. Bellin, J. C. Vallier, A. Allais, and C.E. Bruzek, "First Tests of a 800kJ HTS SMES," IEEE Trans. Appl. Supercond.,vol.18, no.2, pp.1967-1972, Jun. 2008.
  8. L.Gyugyi, "Unified power-flow control concept for flexible AC transmission systems", IEE PROCEEDINGS-C, Vol.139, No.4, JULY 1992
  9. H. Fujita and H. Akagi, "The Unified Power Quality Conditioner: The Integration of Series- and Shunt-Active Filters", IEEE Trans. on Power elctronics, Vol.13, No.2, pp.315- 322, March 1998. https://doi.org/10.1109/63.662847
  10. IEEE Guide for the application of turbine governing systems for hydroelectric generating units, IEEE Standard 1207TM-2004, 2004.