Hybrid 검출방식을 적용한 삼상 선로 응동형 DVR(Dynamic Voltage Restorer) 개발

Development of Three-Phase Line-Interactive Dynamic Voltage Restorer with Hybrid Detection Method

  • 발행 : 2009.10.01

초록

This paper describes the development of a three-phase line-interactive dynamic voltage restorer with hybrid detection method, which is composed of three H-bridge inverter modules and super-capacitors. The operational feasibility was verified through computer simulations with PSCAD/EMTDC software, and experimental works with a 3kVA prototype. The developed system can compensate the input voltage sag and interruption within 2ms. The maximum allowable duration of voltage interruption is about 4 seconds. The developed system can be effectively used to compensate the voltage interruption in the sensitive load, such as computer, communication devices, and automation devices, and medical equipment. The developed system has a simple structure to be easily implemented with commercially available components, and to be highly reliable in operation.

키워드

참고문헌

  1. B. Han, B. Bae, H. Kim, S. Baek, 'Combined Operation of Unified Power Quality Conditioner with Distributed Generation', IEEE Trans, on Power Delivery, Vol.21, No,1, pp,330-338, Jan. 2006 https://doi.org/10.1109/TPWRD.2005.852843
  2. N. Woodley, L. Morgan, A Sundaram, 'Experience with an Inverter-based Dynamic Voltage Restorer', IEEE Trans, on Power Delivery, Vol.14, No.3, pp.1181-1186, July 1999 https://doi.org/10.1109/61.772390
  3. C. Zhan, V. Ramachandaramurthy, A. Arulampalam, C. Fitzer, S. Kromlidis, M, Barnes, N. Jenkins, 'Dynamic Voltage Restorer based on Voltage-Space Vector PWM Control', IEEE Trans, on Industry Applications, Vol.37, No.6, pp.1855-1863, Nov.-Dec. 2001 https://doi.org/10.1109/28.968201
  4. M. Newman, D. Holmes, J. Nielsen, F. Blaabjerg, 'A Dynamic Voltage Restorer with Selective Harmonic Compensation at Medium Voltage Level', IEEE Trans, on Industry Applications, Vol.41, No.6, pp.1744-1753, Nov,-Dec. 2005 https://doi.org/10.1109/TIA.2005.858212
  5. S, Choi, B. Li, D. Vilathgamuwa, 'Design and Analysis of the Inverter-side Filter used in the Dynamic Voltage Restorer', IEEE Trans. on Power Delivery, Vol. 17, No.6, pp.1058-1066, Nov. 2002
  6. C. Fitzer, M. Barnes, P. Green, 'Voltage Sag Detection Technique for a Dynamic Voltage Restorer', IEEE Trans. on Industry Application, Vol.40, No.1, pp.203-212, Jan.-Feb. 2004 https://doi.org/10.1109/TIA.2003.821801
  7. R. Naidoo and P.Pillay, 'A New Method of Voltage Sag and Swell Detection', IEEE Trans. on Power Delivery, Vol.22, No.2, pp.1056-1063, April 2007 https://doi.org/10.1109/TPWRD.2007.893185