초록
The purpose of this study is to evaluate the air diffusion performance of a range of indoor units for room airconditioners; the wall-mounted type, floor-standing type, and ceiling-mounted type. These types of units, which have been widely used in housing spaces, will be studied with respect to thermal comfort and the energy performance using CFD analysis. In this study, current air conditioning status and related problems in housing spaces are examined, and a CFD analysis is performed in order to compare and analyze the thermal comfort and energy efficiency across each type of indoor-unit using the PMV, ADPI, EUC and FCEI indexes. The analysis results collectively considering thermal comfort and energy performance indicated that the ceiling-mounted type 4-way indoor unit showed the best diffusion performance in terms of thermal comfort, and had the second best diffusion performance in terms of energy performance after the wall-mounted type under certain conditions.