Abstract
In order to minimize ac mutual coupling, the auxiliary electrode are located at a right angle in measuring ground impedance. In case that the measurement space is limited, the alternative method is employed. At that time, it is necessary to investigate the measurement errors due to ac mutual coupling and earth mutual resistance in measuring the ground impedances. 'This paper presents the measurement accuracy according to the location of the current and potential auxiliary electrodes in measuring ground impedance of vertically or horizontally buried ground electrode. The measurement errors due to ac mutual coupling were evaluated Consequently, the effect of ac mutual coupling on the measurement accuracy for horizontally buried ground electrode is greater than that for vertically buried ground electrode. Measurement errors due to ac mutual coupling is the largest when the current and potential auxiliary electrodes are located in parallel. The 61.8[%] rule is inappropriate in measuring ground measurement. Theoretically, in case that the angle between the current and potential auxiliary electrodes is 90$[^{\circ}]$, there is no ac mutual coupling. If it is not possible to route the current and potential auxiliary electrodes at a right angle with limitation of measurement space, the location of these electrodes with an obtuse angle is preferred to that with an acute angle in reducing the measurement errors due to ac mutual coupling.
접지임피던스의 측정에서는 교류의 전자유도결합을 최소화시키기 위해 보조전극을 직각으로 설치하며, 측정공간이 제한되는 경우 대안적 방법이 적용되고 있다 이때 접지임피던스의 측정에서는 교류 상호결합과 도전유도에 의한 측정오차를 검토할 필요가 있다. 본 논문에서는 수직 또는 수평으로 매설된 접지극의 접지임피던스를 측정할 때 전류와 전위보조전극의 위치에 따른 측정의 정확도에 관한 것으로 전자유도결합에 의한 측정오차를 평가하였다. 결과적으로 교류 전자유도의 영향을 수직 접지극보다 수평접지극의 경우 크게 나타났으며, 교류 전자유도결합에 의한 측정오차는 전류와 전위보조선이 평행하게 배치되는 경우 가장 크게 나타났으며, 결국 61.8[%]법은 접지임피던스측정에는 부적합하다. 이론적으로 전류와 전위보조전극을 90[^{\circ}]$로 배치하면 전자유도결합은 나타나지 않는다. 측정공간의 제한으로 전류와 전위보조전극을 90[^{\circ}]$로 배치할 수 없는 경우 전자유도에 의한 오차를 저감시키기 위해서는 보조전극을 예각보다는 둔각으로 배치하는 것이 바람직하다.