Abstract
Grounding insures a reference potential point for electric devices and also provides a law resistance path for fault or transient currents in the earth. The ground impedance as a function of frequency is necessary for determining its performance since fault or transient currents could contain a wide range of frequencies. A copper rod electrode is the most commonly used grounding electrode in electric distribution systems. In this paper, the grounding impedance of copper rods has been measured in frequency raging from 60[Hz] up to 100 [kHz] and an equivalent model of the grounding impedance is identified from the measured values. The grounding impedance under study when a typical lightning surge is injected into the grounding system was simulated numerically and graphically through the use of the EDSA software program.
접지시스템은 전기설비의 기준 전위점을 확보할 뿐만 아니라 대지에 낮은 저항으로 고장전류나 과도전류를 흐르게 한다. 주파수에 대한 함수로 접지 임피던스는 고장이나 과도전류가 넓은 범위의 주파수 성분을 포함하기 때문에 접지성능을 평가하는데 필요하다. 동봉은 배전계통에서 가장 많이 쓰이는 접지전극이다. 본 논문에서는 동봉의 접지 임피던스를 주파수 60[Hz] 에서 100[kHz] 범위까지 측정하여 등가 접지임피던스 모델을 구하였다. 뇌격서지가 유입되었을 때 EDSA 프로그램으로 과도접지임피던스의 수치와 파형을 시뮬레이션 하였다.