Abstract

With time, the stable management of turbidity is becoming more important in the water treatment process. So optimization of flocculation is important for the improvement of the sedimentation efficiency. we evaluated the hydrodynamic behavior in the rotation direction (clock-wise, counterclock-wise) of the flocculator in the flocculation basin using Computational Fluid Dynamics (CFD). The results of the CFD simulation, in cases where flocculators rotate in a clockwise direction, a stronger flow is formed near the surface of the water where the rotating direction and current of flow correspond. The variance and standard deviation of the flux are about 8.5 and 2.9 respectively. In contrast, in the case of a counterclockwise direction, a stronger flow is formed near the bottom of the basin. The variance and standard deviation of the flux are about 5.3 and 2.3, respectively. The effluent flux is affected more by the third flocculator spin than the first and second flocculator spins. The third flocculator spinning in the counterclockwise direction is better for the uniform flow of the sedimentation basin than the third flocculator spinning in the clockwise direction

정수처리공정에서 안정적인 탁도 관리가 날이 갈수록 중요해지고 있다. 따라서 침전 효율 향상을 위한 플록형성 공정의 최적화는 매우 중요하다. 우리는 전산유체역학적 방법을 이용하여 플록큐레이터의 회전방향(시계방향, 반시계방향)에 따른 플록 형성지 내 유동특성을 평가하였다. 평가 결과, 플록큐레이터가 시계방향으로 회전하는 경우는 플록큐레이터 회전방향과 수류 흐름이 일치하는 수표면 쪽에서 유동이 강해지고 유출량의 분산 및 표준편차는 각각 8.5, 2.9로 나타났다. 반면에 플록큐레이터가 반시계 방향으로 회전하는 경우는 플록큐레이터 회전방향과 수류 흐름이 일치하는 바닥 쪽에서 유동이 강해지고 유출량의 분산 및 표준편차는 각각 5.3, 2.3으로 나타났다. 또한 플록형성지 유출량은 1,2단 플록큐레이터 회전방향보다는 3단 플록큐레이터의 회전방향에 의해 주로 영향을 받으며 3단 플록큐레이터가 반시계방향으로 회전하는 경우가 시계방향으로 회전하는 경우보다 유출량의 편차가 적기 때문에 침전지의 균등한 흐름을 위해 유리하다.

Keywords

References

  1. 김혜숙, 신미수, 장동순, 정성희, 강동효, "유입구 및 정류벽 최적설계에 의한 최종 침전지 성능 개선 연구," 대한환경공학회지, 27(2), 177-183(2005)
  2. 박세진, 박노석, 임재렴, 김선규, 김석구, 문용택, 방기웅, "CFD를 이용한 첨전지 구조가 수리 거동에 미치는 영향 평가," 대한상하수도학회지, 20(5), 667-676(2006)
  3. 윤재용, 변석종, 이상덕, 김정현, 권순법, "추적자 실험에 의한 정수장 칩전지내 구조물의 수리학적 영향 평가에 관한 연구," 한국수처리기술연구회, 7(1), 11-22(1999)
  4. Reynolds, T. D., Richards, P. A., "Unit operations and processes in environmental engineering," PWs Publishing Company, New York, 181-198(1996)
  5. Krebs, P., "Influence of inlet and outlet configuration on the flow in secondary clarifiers," Water Sci. Technol., 31(2), 181-191(1995) https://doi.org/10.1016/0273-1223(95)00191-O
  6. Cao, Z., Wiley, D. E., Fane, A. G., "CFD simulations of net-type turbulence promoters in a narrow channel," J. Membr. Sci., 185, 157-176(2001) https://doi.org/10.1016/S0376-7388(00)00643-8
  7. Cockx, A., Do-quang, Z., Line, A. & Roustan, M., "Use of computational fluid dynamics for simulating hydrodynamics and mass transfer in industrial ozonation towers," Chem. Eng. Sci., 54(21), 5085-5090(1999) https://doi.org/10.1016/S0009-2509(99)00239-0
  8. Panneerselvam, R., Savithri, S., Surender, G. D., "CFD simulation of hydrodynamics of gas-liquid-solid fluidised bed reactor," Chem. Eng. Sci., 64(6), 1119-1135(2009) https://doi.org/10.1016/j.ces.2008.10.052
  9. Mazzolani, G., Pirozzi, F., and d'Antonoi, G., "A generalized settling approach in the numerical modeling of sedimentation tanks," Water Sci. Technol., 38(3), 95-102(1998) https://doi.org/10.1016/S0273-1223(98)00453-3
  10. Ekama, G. A., Barnard, J. L., Krebs, P., and McCorquofale, J. A., "Secondary settling tanks: theory, modelling, design and operation," JAWQ, 173-175(1997)
  11. Dupont, R., Dahl, C., "A one-dimensional model for a secondary settling tank including density current and shortcircuiting," Water Sci. Technol., 31(2), 215-224(1995) https://doi.org/10.1016/0273-1223(95)00194-R
  12. Bishop, M. M., Morgan, J. M., Cornwell, B., and Jamison, D. K., "Improving the Disinfection time of water plant clear well," AWWA, 85(3), 68-75(1993)