The Optimization for Type "C" LLRT Requirements of Containment Vessel

격납용기 Type "C" 누설률시험 요건 최적화

  • 정남두 (한국수력원자력 원자력발전기술원) ;
  • 김재동 (한국수력원자력 원자력발전기술원) ;
  • 김인철 (한국수력원자력 원자력발전기술원)
  • Published : 2009.03.01

Abstract

The containment local leakage rate testing in nuclear power plants is performed in accordance with ANSI/ANS-56.8(1994) in Korea. Two methods, the make-up flow rate and the pressure decay, are used for LLRT. Though ANSI/ANS-56.8 does not define clearly the minimum test duration for the make-up flow rate method, it requires obtaining the data after reaching the stable condition. Thus the prerequisite stable condition for data acquisition and the test period for type "C" LLRT is differently applied to each NPPs. Therefore, this study presents a unified test criteria for data stabilization and test duration through experiments to improve the test reliability for type "C".