DOI QR코드

DOI QR Code

Cooling Performance Test of the KEPCO HTS Power Cable

  • Yang, H.S. (Korea Basic Science Institute) ;
  • Kim, D.L. (Korea Basic Science Institute) ;
  • Sohn, S.H. (Korea Electric Power Research Institute) ;
  • Lim, J.H. (Korea Electric Power Research Institute) ;
  • Choi, H.O. (Korea Electrotechnology Research Institute) ;
  • Choi, Y.S. (Korea Basic Science Institute) ;
  • Ryoo, H.S. (Korea Electrotechnology Research Institute) ;
  • Hwang, S.D. (Korea Electric Power Research Institute)
  • 발행 : 2009.05.31

초록

The HTS power cable system of 3-phase 100-m class has been tested at the KEPCO's Gochang power testing center in Korea during 8,000 hours or more for investigating long-term operating performance. The system is rated 22.9kV, 1250A and is cooled with sub cooled liquid nitrogen. Several cooling performance tests such as cooling capacity, heat load, AC loss, temperature stability and thermal cycle were performed at operating temperature of 66.4K and several different temperatures.

키워드

참고문헌

  1. H. Yumura, T. Masuda, M. Watanabe, H. Takigawa, Y. Ashibe, H. Ito, M. Hirose and K. Sato "Albany HTS Cable Project Long Term In-Grid Operation Status Update", Advances in Cryogenic Engineering, vol. 53, pp. 1051-1058, 2008 https://doi.org/10.1063/1.2908453
  2. S.H. Sohn, J.H. Lim, S.W. Yim, O.B. Hyun, Hl.R. Kim, K. Yatsuka, S. Isojima, T. Masuda, M. Watanabe, H.S. Ryoo, H.S. Yang, D.L. Kim and S.D. Hwang "The Results of Installation and Preliminary Test of 229kV, 50MVA. 100m Class HTS Power Cable System at KEPCO", IEEE Trans. on Appl. Supercond., vol. 17, pp.2043-2046, 2007 https://doi.org/10.1109/TASC.2007.897764
  3. S.H. Sohn, S.D. Hwang. J.H. Lim, S.W. Yim, O.B. Hyun, H.R. Kim, K. Yatsuka, T. Masuda, S. Isojima, M. Watanabe, H.S. Ryoo, H.S. Yang, D.L. Kim "Verification test of 22.9kV underground HTS cable", Physica C, pp.1146-1149, 2007 https://doi.org/10.1016/j.physc.2007.04.254
  4. H.S. Yang, D.L. Kim, B.S. Lee, Y.S. Choi, S.H. Sohn. J.H. Lim, H.S. Ryoo and S.D. Hwang "Performance Test of Cooling System for KEPCO HTS Power cable", Advances in Cryogenic Engineering, vol. 53, pp. 1067-1072, 2008 https://doi.org/10.1063/1.2908455
  5. J.H. Lim, S. H. Sohn, H.S. Yang, D.L. Kim, H,S. Ryoo, and S.D. Hwang, "The Test Result of Cooling Test on HTS Power Cable of KEPCO", Advances in Cryogenic Engineering, vol. 53, pp.1209-1216, 2008 https://doi.org/10.1063/1.2908475