Abstract
In the present study, the heat transfer characteristics of the fin-tube and PF heat exchangers and the performances of the air-conditioner are experimentally investigated. Also, Cooling Seasonal Performance Factor(CSPF) of the air-conditioner is evaluated. For the heat exchanger experiment, the heat transfer and pressure drop are obtained. For the air-conditioner experiment, the cooling capacity, input power and COP are obtained. The air-enthalpy calorimeter and the constant temperature water bath are used. As the inlet air velocity increases, the heat transfer rate and pressure drop of the heat exchanger increased. PF heat exchanger has smaller refrigerant weight and larger capacity and COP than the fin-tube heat exchanger. The performance of PF-2 heat exchanger with the squarer fin is more excellent than that of PF-1 heat exchanger with the triangler fin. Also, CSPF of the fm -tube and PF heat exchanger is evaluated.
본 연구에서는 핀-관 열교환기와 PF 열교환기의 열전달 특성과 이를 적용한 공조기의 성능을 비교 조사하였다. 또한 공조기의 냉방기간 에너지효율(CSPF)을 평가하였다. 열교환기 실험을 위해 3종류의 열교환기에 대한 열전달 및 압력강하를 그리고 공조기 성능평가를 위해 냉방표준, 냉방저온에서 냉방능력, 소비전력, COP를 산출하였다. 실험은 칼로리미터와 항온수조를 사용하여 수행되었다. 유입공기 속도가 증가함에 따라 열교환기의 열전달율과 압력강하는 증가하였다. PF 열교환기 적용 시스템의 적정 냉매량은 핀-관공조기보다 약 $15{\sim}20%$ 감소하였으나, 냉방능력은 증가, 소비전력은 감소하여 COP는 향상되었다. 사각형 핀을 가진 PF 열교환기가 삼각형 핀보다 냉방능력과 COP가 더 우수하였다. 실환경 온도조건을 반영하기 위해 PF 열교환기와 핀-관 열교환기 적용 시스템의 CSPF가 계산되었다.