Abstract
The new method is proposed to improve the dynamics of the phase angle detector during abrupt voltage dip caused by a grid fault. Usually, LPF(low pass filter) is used in the feedback loop of SRF(Synchronous Reference Frame) - PLL (Phase Locked Loop) system because the measured grid voltage contains harmonic distortions and sensor noises. A better transient response can be obtained with the proposed design method for SRF-PLL by the analysis of linearized model of the PLL system including LPF. Furthermore, in the proposed method, the controller gain and LPF cut-off frequency are changed from normal value to transient value when the voltage disturbance is detected. This paper shows the feasibility and the usefulness of the proposed methods through the computer simulation and the experiment.
전원사고로 인하여 야기되는 전원급변상황에서 위상각의 새로운 PLL 방법은 추종속도를 개선시키기 위하여 제안되었다. 일반적으로 측정된 전원이 이상적이지 않고 고조파가 포함되어 있으며 센서의 노이즈 때문에 동기좌표계 PLL의 피드백 루프에는 LPF를 사용하고 있다. 그러므로 과도상태의 빠른 동특성을 얻기 위해서 LPF를 고려한 PLL시스템의 모델링을 제안하였다. 또한 전원의 급변 시에 빠른 위상각 검출을 위한 방법으로 자동으로 제어기 대역폭과 LPF의 차단주파수를 변동시키는 가변 파라미터 PLL방법을 제안하였다. 이를 시뮬레이션과 실험을 통해 검증하여 유효성을 보이고자 한다.