A Study on Fire Resistance and Spalling of HPC Beam with Fiber-Cocktail in ISO Fire under Loading Condition

표준화재 재하조건하에서 Fiber Cocktail을 혼입한 고강도 콘크리트 보의 폭렬특성 및 내화성능에 관한 연구

  • Published : 2009.12.31

Abstract

In an attempt to control the spalling in high strength concrete, spalling reducer was mixed to identify the effect and thermal characteristics of concrete beam member at high temperature. The member was manufactured in such as way of adding 40~60MPa of high strength concrete into spalling reducer, and then fire resistance performance were monitored under the ISO standard fire load condition in accordance with KS F 2257. As a result of test, fore rate performance of 40MPa beam without spalling reducer was 180minutes, 50MPa was 174minutes and 60MPa was 152minutes, indicating that 50MPa and 60MPa beam appeared 6~28minutes short to become a 3-hour rate. However, 50 and 60MPa beam mixed with spalling reducer appeared to have satisfied the requirements for 180minutes. A spalling was occurred in surface of 50 and 60MPa beam mixed without spalling reducer, while no spalling or surface failure was occurred with 50 and 60MPa beam mixed with spalling reducer. Thus polypropylene fiber mixed with the concrete proved to be effective, but viewing that the surface of 60MPa was peeled off partially, the steel fiber mixed appeared not to be effective for the beam more than 60MPa.

본 연구는 고강도 콘크리트의 폭렬 발생을 제어하기 위하여 폭렬 저감재를 혼입함에 따른 폭렬 저감효과를 살펴보고 콘크리트 보 부재의 고온 가열시의 열적 특성을 평가하기 위하여 실시하였다. 이에 고강도 콘크리트 40~60MPa를 폭렬 저감재를 혼입하여 부재를 제작하였으며, KS F 2257의 ISO 표준화재 재하조건에서의 내화성능을 살펴보았다. 실험결과 폭렬 저감재를 혼입하지 않은 40MPa은 180분, 50MPa 174분, 60MPa 152분으로 50, 60MPa보는 기준에서 정하는 3시간 내화성능에 6~28분 부족한 것으로 나타났다. 그러나 폭렬 저감재를 혼입한 50, 60MPa 보는 모두 법에서 정하는 내화 성능 시간인 180분을 만족하였다. 폭렬 저감재를 혼입하지 않은 50, 60MPa의 콘크리트 보는 화재에 노출된 모든 면에서 폭렬이 발생되었으나 폭렬 저감재를 혼입한 50, 60MPa 보에서는 표면탈락 및 폭렬은 거의 발생되지 않았다. 따라서 콘크리트의 폭렬 방지를 위해 혼입한 PP섬유는 폭렬 방지 효과를 나타내고 있으나 60MPa 표면이 일부 탈락 된 것으로 보아 표면 탈락 방지를 위해 혼입한 강섬유는 60MPa 이상의 강도에서는 크게 효과가 나타나지 않았다.

Keywords

References

  1. British Standards Institution, 'BS 7974 Application of Fire Safety Engineering Principles to the Design of Building-Code of Practice'(2001)
  2. Philip J. Dinenno, P.E. et al, 'SFPE Handbook of Fire Protection Engineering', National Fire Protection Association and Society of Fire Protection Engineers(1988)
  3. V.H. Patrick and T. Heimo, 'Description of Swedish System of Fire Performance Based Regulation and Temperature Analysis of Structural Sections'(2003)
  4. B.R. Kirby, 'Natural Fires in Large Scale Compartments-A British Steel Technical', Fire Research Station Collaborative Project(1994)
  5. K.D. Hertz, 'Limits of Spalling of Fire-exposed Concrete', Fire Safety Journal, pp.103-116(2003) https://doi.org/10.1016/S0379-7112(02)00051-6
  6. T. Harada, 'Strength, Elasticity and Thermal Properties of Concrete Subjected to Elevated Temperatures', ACI SP-34, Vol.1, p.393(1972)
  7. CEN, 'Eurocode 3. Design of Steel Structure Part 1.2: General Rules Structural Fire Design', pp. 15-21(1995)
  8. European Committee for Standardization, 'ENV 1994 -1-2: Eurocode 4: Design of Composite Steel and Concrete Structures. Part 1.2: General Rules:Structural Fire Design', Brussels(1994)
  9. John A. Purkiss, 'Fire Safety Engineering Design of Structures', Butterworth-Heinemann(1966)
  10. W.A. Morris, 'Guidelines for the Construction of Fire-resisting Structural Elements', Building Research Establishment Report(1998)
  11. Y. Anderberg, 'Spalling Phenomena of HPC and OC', NIST Workshop on Fire Performance of High Strength Concrete in Gaithersburg(1997)
  12. J.M. Franssen, 'Failure Temperature of a System Comprising a Restrained Column Submitted to Fire', Fire Safety Journal, Vol.34, pp.191-207 (2000) https://doi.org/10.1016/S0379-7112(99)00047-8
  13. U.M. Jumpannen, 'Effect of Strength on Fire Behaviour of Concrete', Nordic Concrete Research (1989)
  14. V.K.R. Kodur, 'Design Equations for Evaluating the Fire Resistance of SFRC Filled Steel Columns', Journal of Structural Engineering. ASCE, Vol.124, No.6, pp.671-677(1998) https://doi.org/10.1061/(ASCE)0733-9445(1998)124:6(671)
  15. T.T. Lie, 'Fire Resistance of Circular Steel Columns Filled with Bar-reinforced Concrete', Journal of Structural Engineering, ASCE, Vol.120, No.5, pp.1489-1509(1994) https://doi.org/10.1061/(ASCE)0733-9445(1994)120:5(1489)
  16. L.T. Phan, 'High-strength Concrete at High Temperature:An Overview', Proceedings of 6th International Symposiumon Utilization of High Strength/High Performance Concrete, Leipzig, Germany, pp.501-518(2002)
  17. C.G. Bailey, 'Simulation of the Structural Behaviour of Steel-Framed Buildings in Fire', PhD Thesis, University of Sheffield(1995)
  18. J. Cai, 'Developments in Modelling of Composite Building Structures in Fire', PhD thesis, University of Sheffield(2002)
  19. J. Kal, 'Modelling of Asymmetric Cross-section Members for Fire Conditions', Department of Civil and Structural Studies, The university of Sheffield (2001)
  20. 김형준, 한상훈, 최승관, '화재시 콘크리트요소 폭렬 영향성 고찰', 화재소방학회 논문지, Vol.21, No. 2, pp.54-63(2007)
  21. 김흥열, 채한식, 전현규, 염광수, 'Fiber Cocktail을 혼입한 고강도 콘크리트의 고온시 변형특성 및 모델제시에 관한 실험적 연구', 한국콘크리트 학회 학술대회 발표논문집, Vol.19, No.2(2007)
  22. 김흥열, 채한식, 전현규, 염광수, 'Fiber Cocktail을 혼입한 고강도 콘크리트의 고온시 압축강도특성 및 모델제시에 관한 실험적 연구', 한국콘크리트 학회 학술대회 발표논문집, Vol.19, No.2(2007)
  23. 김흥열, 채한식, 전현규, 염광수, 'Fiber Cocktail을 혼입한 고강도 콘크리트의 고온시 탄성계수특성 및 모델제시에 관한 실험적 연구', 한국콘크리트 학회 학술대회 발표논문집, Vol.19, No.2(2007)
  24. 김흥열, '고온가열시 콘크리트의 역학적 특성에 관한 실험적 연구', 대한건축학회 논문집, Vol.8, No.118 (2002)
  25. 김흥열, 전현규, 'Fiber-Cocktail 혼입에 따른 고강도 콘크리트 구조부재의 내화성능에 관한 실험적 연구' 한국콘크리트 학회 학술대회 발표논문집, Vol.19, No.1 (2007)
  26. 김흥열, 채한식, 김형준, 전현규, 염광수, '표준화재 재하조건에서 Fiber Cocktail을 혼입한 고강도 콘크리트 기둥의 강도별 전열특성에 관한 연구', 한국콘크리트 학회 학술대회 발표논문집, Vol.20, No.1(2008)
  27. 김흥열, 채한식, 김형준, 전현규, 염광수, '표준화재 재하조건에서 Fiber Cocktail을 혼입한 고강도 콘크리트 기둥의 강도별 화재거동에 관한 연구', 한국콘크리트 학회 학술대회 발표논문집, Vol.20, No.1(2008)