Real Time Wide Area Voltage Stability Index in the Korean Metropolitan Area

  • Han, Sang-Wook (School of Electrical Engineering, Korea University) ;
  • Lee, Byong-Jun (School of Electrical Engineering, Korea University) ;
  • Kim, Sang-Tae (Korea Electrical Power Data Network(KDN)) ;
  • Moon, Young-Hwan (Electric Power Research Division, Korea Electrotechnology Research Institute(KERI))
  • Published : 2009.12.01

Abstract

Through the development of phasor measurement units (PMU), various aspects of power system dynamic behavior could be monitored and diagnosed. Monitoring dynamic voltage stability has become one of the achievements we can obtain from PMUs. It is very important to select the most appropriate method for the Korea Electric Power Corporation (KEPCO) system since there are many voltage stability indices. In this paper, we propose an advanced WAVI (Wide Area Voltage Stability) that is well suited for the purposes of monitoring the dynamic voltage stability of KEPCO's PMU installation plan. The salient features of the proposed index are: i) it uses only PMU measurements without coupling with EMS data; ii) it is computationally unburdened and can be applied to real-time situations. The proposed index is applied to the KEPCO test system and the results show that it successfully predicts voltage instability through comparative studies.

Keywords

References

  1. D. E. Julian, R. P. Schulz, K. T. Vu, W. H. Quaintance, N. B. Bhatt, and D. Novosel, 'Quantifying Proximity To Voltage Collapse Using The Voltage Instability Predictor (VIP),' 2000 IEEE, July 2000
  2. Mats Larsson, and Joachim Bertsch, 'Monitoring and Operation of Transmission Corridors,' Power Tech Conference Proceedings, 2003 IEEE, Bologna, pp. 8 vol. 3, 23-26 June 2003
  3. Mats Larsson, Christian Rehtanz, and Joachim Bertsch, 'Real-Time Voltage Stability Assessment Of Transmission Corridors,' IFAC, 2003
  4. Khoi Tien Vu, and Damir Novosel, ' Voltage instabil- ity predictor (vip)-method and system for performing adaptive control to improve voltage stability in powersystems,' United States Patent, May 15,1998
  5. B. Xu, and A. Abur, ' Observability Analysis and Measurement Placement for Systems with PMUs,' IEEE paper 0-7803-8718-X/04, pp, 1-4, 2004
  6. S. T. Kim, J. Y. Kim, N. C. Yu, D. C. Lee, Y. H. Moon, T. H. Kim, B. Lee, and S. W. Han, ' Development ofK-WAMS for Monitoring Korean Power Grid Security, and Application to the Future IT Infrastructure Design,' CIGRE, C2-103, 2008
  7. T. L. Baldwin, L. Mili, M. B. Boisen, and R. Adapa, ' Power system observability with minimal phasor measurement placement,' IEEE Transactions on Power Systems, 8, No. 2, pp. 707-715, May 1993 https://doi.org/10.1109/59.260810
  8. A. R., Khatib, R. F. Nuqui, M. R. Ingram, and A. G. Phadke, ' Real-time estimation of security from voltage collapse using synchronized phasor mεasurements,' IEEE paper 0-7803-8465-2/03, 2004
  9. C. Rehtanz, and J. Bertsch, 'A new wide area protection system,' in Bulk Power System Dynamics and Control V, August 26-31 , 2001
  10. A. Miguel, and G. Carlos, 'Phasor measurement unit (PMUs) application in the transmission network of CFE Mexico,' CIGRE, 21, rue d’Artois, F-75008 Paris, B5-210, 2006
  11. D. Cirio, A. Danelli, M. Pozzi, S.Cecere, G.Giannuzzi, and M. Sfoma, 'Wide area monitoring and control system: the ltalian research and development,' CIGRE, 21, rue d’Artois, F-75008 Paris, C2-208, 2006
  12. S. Bruno, M. De Benedicts, and M. La Scala, 'Emergency control assessment for mitigating the effects of cascading outages,' CIGRE, 21, rue d’Artois, F-75008 Paris, C2-209, 2006

Cited by

  1. A study of the application of fast valving and braking resistor for an intelligent SPS vol.53, 2013, https://doi.org/10.1016/j.ijepes.2013.05.049
  2. Centralized Adaptive Under Frequency Load Shedding Schemes for Smart Grid Using Synchronous Phase Measurement Unit vol.8, pp.3, 2013, https://doi.org/10.5370/JEET.2013.8.3.446