Abstract
This paper analyzes a asymmetry current with SFCL (Superconducting Fault Current Limiter) operation during transient period, when a fault occurs in power systems. The principle of asymmetry current nature is reviewed and asymmetry components reduction with SFCL operation is explained. To verify the performance of SFCL, a EMTP/ATPDraw model of SFCLs using MODELS language developed and simulated. Throughout the simulation, results presents the main factors for reducing the asymmetry component of fault current are not a quenching time, but a limiting resistance of SFCL and fault initiated angle.