입자 제거용 환기 필터의 설계 변수 선정 기법을 위한 이론 및 실험적 연구

Theoretical and experimental study for optimization method of particle removal fibrous filter used in ventilation system

  • 정의경 (연세대학교 기계공학부) ;
  • 노광철 (연세대학교 기계공학부) ;
  • 박재홍 (연세대학교 기계공학부) ;
  • 황정호 (연세대학교 기계공학부)
  • Jung, Yee-Kyeong (Department of Mechanical Engineering, Yonsei University) ;
  • Noh, Kwang-Chul (Department of Mechanical Engineering, Yonsei University) ;
  • Park, Jae-Hong (Department of Mechanical Engineering, Yonsei University) ;
  • Hwang, Jungho (Department of Mechanical Engineering, Yonsei University)
  • 발행 : 2009.03.31

초록

Pressure drop and particle removal efficiency of two commercial fibrous medium filters were measured with 20~1,000 nm sized aerosolized KCl particles. Pressure drop and particle removal efficiency were also theoretically predicted and the results qualitatively agreed with the experimental data. For this given particle removal efficiency, a filter design method for obtaining minimum pressure drop (and therefore minimum fan power) was suggested in this study by selecting solidity and fiber diameter as parameters. Therefore, by carrying out theoretical and experimental approaches together, this paper introduced a way of finding conditions for low pressure drop and high performance of a fibrous filter, especially if the filter would be used in mechanical ventilation system.

키워드