Abstract
The ELectromagnetic Core Imperfection Detector (EL-CID) test was performed on a small generator in the laboratory and a gas turbine generator in the field to assess the fault condition of generator stator core. Artificial defects with six different sizes were introduced in the small generator. The scan results on six defects show a very large increase in the magnitude of fault current compared to that obtained with a healthy core. After the stator core heats up, a thermal imaging camera was used to detect hot spot on the inner surface of the core for comparison. Several faults were found during inspection of the gas turbine generator with the EL-CID. It has been shown that the existence of a fault can be determined by monitoring the magnitude of fault current.