초록

Analysis of the partial discharge signal, a technique to diagnose the stator winding insulation is a key function for the diagnosis of high voltage rotating machines and requires high precision. To satisfy this requirement, various denoising techniques such as filtering and differential methods were proposed. However, these techniques can not eliminate a adjacent induction noise that decreases reliability of the diagnosis. A simple novel denoising algorithm, therefore, is proposed for removing the adjacent induction noise in this paper. The algorithm shows good performance in the real partial discharge signals measured by 13kV class capacitive couplers installed at hydro-generator in Dae-cheong Dam.

키워드

참고문헌

  1. 강동식 외, '고압 회전기 On-line 부분방전 측정용 Ceramic Coupler 특성', 대한전기학회 논문지, Vol.51C, No. 5, pp.205-212, 2002
  2. Wilfried Hutter, 'Partial Discharge Detection in Rotating Electrical Machines' , IEEE Electrical Insulation Magazine, Vol. 8, No.3, pp. 21 ~ 32, May/June 1992 https://doi.org/10.1109/57.139068
  3. A. Wilson, RJ. Jackson, 'Discharge Detection Techniques for Stator Windings', lEE Proceedings, Vol. 132, Part B, No.5, pp. 234-244, September 1985
  4. I. M. Culbert, H. Dhirani and G. C. Stone, 'Handbook to Assess the Insulation Condition of Large Rotating Machines', EPRI Publication EL-5036, Vol. 16, June 1989
  5. 강동식 외, '13 KV급 수력발전기 고정자 권선용 On-line 부분방전 측정 시스템 개발 및 현장적용 평가', 대한전기학회 논문지, Vol. 55, No. 4, pp 189-198, 2006
  6. R E. James and B. T. Phung, 'Development of Computer-based Measurements and their Application to PD Pattern Analysis', IEEE Transactions on Dielectrics and Electrical Insulation, Vol. 2, No.5, October 1995 https://doi.org/10.1109/94.469978